The Aegis Sequencer can be connected to external BMS (BAS) in two different protocols:
1) BACnet
2) Modbus
In the case of Modbus, both RTU or TCP/IP communication is available.
a) RTU: connection using two wires directly to serial port in the Sequencer.
b) TCP/IP: connection using a port in the network switch.
In the case of BACnet, connection is made to the available port in the network switch. Not every individual unit
communication point will be available through the Sequencer. Available points are shown in the table below.
Version 1.3 BACnet Server Configuration Settings
Device Instance
Timeout
Command Timeout
General Mng. Object Instance BACnet
3000
1500
Export ID
Type
Object Instance
Variable
0
BinaryValue
1
UnitOn
1
BinaryValue
2
GlbAlrm
2
BinaryValue
3
AntilegionellaFunction.Active
3
BinaryValue
4
SecondaryPumpFunction.WaterPumpDigitalOut
4
BinaryValue
5
AntilegionellaFunction.Phase2Running
5
BinaryValue
6
ID1.Val
6
BinaryValue
7
ID2.Val
7
BinaryValue
8
OnOffUnitMng.BmsOnOff
8
BinaryValue
9
AlarmMng.AlrmResByBms
9
BinaryValue
10
AntilegionellaFunction.StartManual
10
BinaryValue
11
AntilegionellaFunction.StopManual
11
BinaryValue
12
AL_Manager_Probe_BT1.Active
12
BinaryValue
13
AL_Manager_Probe_BT2.Active
13
BinaryValue
14
AL_Manager_Probe_SecPump.Active
14
BinaryValue
15
AL_Manager_Probe_Antilegionella.Active
15
BinaryValue
16
AL_Manager_Probe_Step2.Active
16
BinaryValue
17
AL_Manager_Probe_Step3.Active
17
BinaryValue
18
AL_Manager_Probe_Step4.Active
18
BinaryValue
19
AL_Manager_Probe_Step5.Active
19
BinaryValue
20
AL_Manager_Probe_Step6.Active
20
BinaryValue
21
AL_Manager_DI.Active
21
BinaryValue
22
AL_Offline_U1.Active
22
BinaryValue
23
AL_Offline_U2.Active
23
BinaryValue
24
AL_Offline_U3.Active
24
BinaryValue
25
AL_Offline_U4.Active
25
BinaryValue
26
AL_Offline_U5.Active
26
BinaryValue
27
AL_Offline_U6.Active
27
BinaryValue
28
AL_U1.Active
28
BinaryValue
29
AL_U2.Active
29
BinaryValue
30
AL_U3.Active
30
BinaryValue
31
AL_U4.Active
31
BinaryValue
32
AL_U5.Active
32
BinaryValue
33
AL_U6.Active