6. Alarm Management
6.1. Alarm Screens and LED
Pressing the ALARM key can result in two different scenarios, depending on whether an alarm is
active. If there is no active alarm, the following screen is displayed:
This screen makes it possible to easily go to the alarms log using the ENTER key
(see section 6.2.
).
If there is at least one alarm, the alarms screen is sorted by alarm code from lesser to greater impact to
the system. For instance, If one of the temperature probes is disconnected the sequencer turns off all
units and so is listed first. An alarm to a single unit is listed afterwards as the sequencer can still have
other units operating.
In every alarm screen, the alarms log can be displayed by pressing ENTER. The red LED under the ALARM
button will display as follows:
•
Off:
no active alarm
•
Flashing:
at least one active alarm, display shows a screen that is not part of the alarms loop.
•
On:
at least one active alarm, and a screen that is part of the alarms loop is displayed.
From the last menu of the loop it is possible to reset the active alarms by pressing and holding the alarm
key for 3 seconds.