Go to d. Network Configuration tab and press enter.
IV.
Input the following settings:
•
Enable: Static
•
Set IP address to 192.168.1.152
•
MASK: 255.255.255.000
•
GW: 192.168.1.1
•
DNS: 192.168.1.1
6. Search and record the IP address of each Aegis A heat pump being connected to the sequencer.
Set the Slave parameters to match the IP address of each unit in order. To set these parameters
for each unit:
I.
Press program button PRG or the button on the remote interface of the Sequencer.
II.
Enter Service password 0077.
III.
Scroll down to Slaves parameters.
IV.
Change the IP address of the unit inside the Sequencer to match the IP address on each
heat pump.