27
ENGLISH
Trouble shooting - alarms - faults.
Indication Cause
Solution
No LED lit up
No power supply, leak detector
Make sure of the power supply
not powered
to the home
Make sure that the electrical con-
nection has been made accor-
ding to the wiring diagram, make
sure that the electrical power
supply reaches the terminals.
If the problem persists, call the
technical service (the leak detec-
tor is not provided with fuses, do
not break the safety seal)
All LEDs flashing in rotation
Leak detector in warm-up phase
Wait for 2.5 minutes until the end
of the automatic warm-up proce-
dure
Green LED lit up,
Normal operation
Leak detector is in normal
all others unlit
operation
Green LED lit up,
Fault found in the electronic
In the case of installation in
yellow LED lit up
circuit or sensor
network of two or more sensors,
the fault of a slave is given on the
master: if the fault is on a slave,
the master has the green LED
flashing, check the slave and not
the master. Send the faulty detec-
tor to technical service department
WATTS 8FI/GS022A
F