984GD (Globe) Pump Control Control Valve with Rate-of-Flow Feature

2          IOM-A-ACV-984_684   2115 

EDP# 1917098 

© 2021 Watts

Standard Components

1

X

X

Y/FC

2

9

4

7

6

X

X

5

5

CLOSES VALVE

OPENS VALVE

FLOW

3(L)

8

Installation

1.  Prior to installation, flush line to remove debris.
2.  Install valve so the flow arrow matches flow through the line, and gauges to monitor valve inlet and outlet pressures. A Position Indicator 

can be installed to provide visual indication of valve position and operation without disassembly.

3.  Install isolation valves upstream and downstream of the main valve.
4.  Provide adequate clearance for valve servicing and maintenance. Refer to valve servicing dimensions on next page. Avoid installing valves 

6" and larger in the vertical position (main valve stem horizontal). Automatic Control Valves (ACVs) are designed for horizontal in-line instal-

lation, with the cover facing up (main valve stem vertical). Slow operation or premature stem and guide wear may occur if valve is not 

installed according to factory recommendations. Consult factory for detailed engineering review prior to ordering if valve is to be installed 

other than horizontally in-line.

5.  If valve is equipped with a pilot control system, extra precautions should be made during installation to protect the piping circuit from dam-

age. Only remove the pilot control system from the valve if necessary. Tubing and fittings should be kept clean and replaced exactly as 

removed. Consult appropriate hydraulic schematic to ensure proper re-assembly.

6.  Connect solenoid wiring leads to desired switching device, using safe, standard electrical practices.
7.  Wire the limit switch contacts to the proper relay connections, using safe, standard electrical practices. Adjust the limit switch collar to the 

approximate make/break contact position.

8.  After installation, vent entrapped air from valve cover and pilot system by following instructions on Technical Bulletin.
9.  Field install downstream orifice plate assembly pressure sense lines per schematic. 

 

– To accurately set flow rates, either a differential gauge or a flow meter should be installed. 

 

– Check orifice plate to assure that sense holes are free from obstruction.

Start-up of an automatic control valve requires that proper procedures be followed. Time must be allowed for the valve to react to adjustments and the 
system to stabilize. The objective is to bring the valve into service in a controlled manner to protect the system from damaging over-pressure.

Operation

The Pump Control Valve with Rate-of-Flow Feature is designed to 

minimize the surges associated with the starting and stopping of 

pumps. The valve slowly opens and closes as required to control 

pumping related surges, and throttles to maintain a maximum flow 

rate during the pumping cycle. The pump starts and stops against a 

closed valve. 

Pump Start Up: 

When the pump is signaled to start, the 3-Way 

Solenoid is energized, directing pressure into the cover chamber of 

the 3-way Accelerator Pilot. The Accelerator Pilot allows the main 

valve cover chamber to be vented downstream, causing the valve 

to open at a controlled rate, gradually admitting pumping pressure 

into the distribution system. The rate of opening is controlled by the 

adjustable opening speed control, which restricts the speed of fluid 

and pressure evacuating the main valve cover chamber. The valve 

remains open during the pumping cycle. 

Rate-of-Flow Feature: 

During the pumping cycle, the valve acts 

as a Rate-of-Flow Control Valve. Throttling (Flow Control) action is 

controlled by a normally open, differential control pilot designed to: 

1) Open (allowing fluid out of the main valve cover chamber) when 

the differential pressure across the orifice plate is below the adjust-

able set point, and, 2) Close (allowing fluid to fill the main valve cover 

chamber through the integral orifice of the Accelerator Pilot) when the 

differential pressure across the orifice plate is above the adjustable set 

point. A decrease in differential pressure causes the valve to modulate 

towards an open position, increasing flow rate. An increase in differen-

tial pressure causes the valve to modulate towards a closed position, 

decreasing flow rate. 

The Orifice Plate Assembly should be installed three to five pipe diam-

eters downstream of the Pump Control Valve, and field connected 

with 3/8” minimum copper tubing in accordance with factory piping 

schematic. 

Please specify desired flow rate PRIOR to ordering.

 

Pump Shutdown:

 When the pump is signaled to turn off, the 3-Way 

Solenoid is de-energized, venting the cover chamber of the 3-way 

Accelerator Pilot. The Accelerator Pilot allows the main valve cover 

chamber to be connected to upstream pressure, causing the valve to 

close at a controlled rate. The valve slowly begins to close while the 

pump continues to operate. The closing rate of the valve is controlled 

by the adjustable closing speed control, which restricts the speed of 

fluid and pressure entering the main valve cover chamber. When the 

valve reaches the closed position, the limit switch is actuated, turning 

the pump off. 

Hydraulic Check Feature: 

When the pump is turned off and down-

stream pressure is greater than upstream pressure, downstream pres-

sure is admitted to the main valve cover chamber through a check 

valve in the pilot control system, closing the valve, preventing reversal 

of flow. 
Manual Operation: Engaging the Solenoid Manual operator simulates 

power to the solenoid, manually opening the main valve. Disengaging 

the Solenoid Manual operator returns the valve to the closed position.

1 – Main Valve (905GD – Single Chamber)

2 – Model 22 Accelerator Control

3 – Limit Switch

4 – 3-Way Solenoid

5 – Check Valve

6 – Adjustable Opening Speed

7 – Adjustable Closing Speed

8 – Rate-of-Flow Control

9 – Orifice Plate Assembly

Y – Y-Strainer 

X – Isolation Cocks

Summary of Contents for AMES 984GD

Page 1: ...missioning the Pump Control Valve 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to the...

Page 2: ...and stops against a closed valve Pump Start Up When the pump is signaled to start the 3 Way Solenoid is energized directing pressure into the cover chamber of the 3 way Accelerator Pilot The Accelerat...

Page 3: ...OUT position See Figure 1 STEP 2 Loosen a tube fitting or cover plug at the main valve to allow air to vent during start up STEP 3 Energize the solenoid to check actuation and to confirm connec tion t...

Page 4: ...lockwise increasing the rate of opening See Figure 3B If valve opening is too quick turn the adjustment screw IN clock wise decreasing the rate of opening See Figure 3A STEP 11 De energize the solenoi...

Page 5: ...ve specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphr...

Page 6: ...Valve will not close Closed isolation valves in pilot system Check isolation valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem assembl...

Page 7: ...Remove cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may requi...

Page 8: ...e brush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thr...

Page 9: ...mooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrity of the Seat Seal by following the Seat Seal Test procedure in previous section 12 Return valv...