background image

4          IOM-A-ACV-984_684   2115 

EDP# 1917098 

© 2021 Watts

IOM-A-ACV-984_684   2115 

EDP# 1917098 

© 2021 Watts         5

STEP 7

Slowly open downstream isolation valve to establish flow through 
the system.

STEP 8

With a demand for flow on the system, the valve can now be 
adjusted for the proper flow rate. This requires a meter to read the 
flow that the valve is providing.

STEP 9

While reading the meter register, adjust the Rate of Flow Control:

Turn the adjustment screw IN, clockwise, to increase the flow rate 
regulated (See Figure 2A).

Turn the adjustment screw OUT, counterclockwise, to reduce or 
lower the flow rate regulated (See Figure 2B).

Setting the Rate-of-Flow Control

STEP 10

Opening Speed Flow Control Adjustment: 

The Opening speed 

flow control allows free flow into the cover and restricted flow out 
of the cover of the main valve. 

If valve opening is too slow, turn the adjustment screw OUT, 
counterclockwise, increasing the rate of opening (See Figure 3B).

 If valve opening is too quick, turn the adjustment screw IN, clock-
wise, decreasing the rate of opening (See Figure 3A).

STEP 11

De-energize the solenoid to check that the main valve closes.

STEP 12

Closing Speed Needle Valve Adjustment: The closing speed 
needle valve regulates fluid pressure into the main valve cover 
chamber, controlling the valve closing speed.

If valve closing is too slow, turn the adjustment screw OUT, coun-
terclockwise, increasing the rate of closing. 

STEP 12

At valve closure booster pump will stop. Adjust limit switch collar 
to final position to ensure positive actuation of limit switch elec-
trical contact, if necessary, by sliding up/down to location (See 
Figure 4).

Figure 4 

Limit Switch in Closed Position

Counterclockwise to INCREASE 

the rate of opening

Clockwise to DECREASE 

rate of opening

3A

3B

Figure 3 

Flow Control

Counterclockwise to REDUCE  

Flow Rate Regulated

Clockwise to INCREASE 

Flow Rate Regulated

2A

2B

Figure 2 

CP14-1 Rate-of-Flow Control Pilot

Summary of Contents for AMES 984GD

Page 1: ...missioning the Pump Control Valve 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to the...

Page 2: ...and stops against a closed valve Pump Start Up When the pump is signaled to start the 3 Way Solenoid is energized directing pressure into the cover chamber of the 3 way Accelerator Pilot The Accelerat...

Page 3: ...OUT position See Figure 1 STEP 2 Loosen a tube fitting or cover plug at the main valve to allow air to vent during start up STEP 3 Energize the solenoid to check actuation and to confirm connec tion t...

Page 4: ...lockwise increasing the rate of opening See Figure 3B If valve opening is too quick turn the adjustment screw IN clock wise decreasing the rate of opening See Figure 3A STEP 11 De energize the solenoi...

Page 5: ...ve specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphr...

Page 6: ...Valve will not close Closed isolation valves in pilot system Check isolation valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem assembl...

Page 7: ...Remove cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may requi...

Page 8: ...e brush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thr...

Page 9: ...mooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrity of the Seat Seal by following the Seat Seal Test procedure in previous section 12 Return valv...

Page 10: ...s Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 13 Seat Disc Buna N Nitrile 14 Spacer...

Page 11: ...IOM A ACV 984_684 2115 EDP 1917098 2021 Watts 11 NOTES...

Page 12: ...Watts USA Backflow T 978 689 6066 F 978 975 8350 AmesFireWater com USA Control Valves T 713 943 0688 F 713 944 9445 AmesFireWater com Canada T 888 208 8927 F 905 481 2316 AmesFireWater ca Latin Ameri...

Reviews: