Benchmark 5000-6000 Boiler Installation & Startup Manual
SECTION 6:
BOILER SEQUENCING TECHNOLOGY
OMM-0123_E
• GF-207 • 12/17/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
80
of
95
6.3.2 OPTION 2 - Constant Setpoint With Modbus Wired Header
Sensor
OPTION 2 - Constant Setpoint With Modbus Wired Header Sensor Instructions
Step 1: MODbus Header Sensor Wiring
1.
Using Shielded pair 18 - 22 AWG cable, connect the Temperature Transmitter (P/N
65169
)
terminal Pin B to the RS485+ terminal on the I/O Box of any of the Boiler units, and Pin A of
the Temperature Transmitter to the RS485- terminal on the I/O Box of any of the Boiler
units.
2. Using Shielded pair 18 - 22 AWG cable, connect the Modbus Header Temperature Sensor
(P/N 24410) to pins 2 and 3 of the Temperature Transmitter.
3. Install a jumper wire between pins 1 and 2 of the Temperature Transmitter.
NOTES:
•
Polarity must be observed for the RS485 connections.
•
The ground for the shield is at the “SHLD” terminal in the I/O the Box.
•
The header sensor must be installed between 2 and 10 feet (0.61 and 3.1m)
downstream of the LAST boiler in the plant’s supply water header.
•
There is no polarity to be observed. The ground for the shield is at the power supply
ground. The sensor end of the shield must be left free and ungrounded.
Step 2: Configure ALL C-More Units
On ALL Boilers:
1. Go to the
Configuration
menu and set the BST Menu item to
Enabled
.
2. Go to the Boiler Sequencing Menu and set the BST Mode item to
BST Client
(for now).
On MANAGER only:
3. Go to the BST Setpoint item and enter the desired Setpoint.
4. Go to the BST Setup Menu item and set to
Enabled
.
5. Go to the BST Setpoint Mode item and select
Constant Setpoint
.
6. Go to the Head Temp Source item and select
Network
.
7. Go to the Header Temp Addr item and enter the Modbus Address (240).
8. Go to the Header Temp Point item and enter the Modbus Point (14).
When ALL C-More units have been configured:
9. Go to the Boiler Sequencing Menu of the Manager unit and set the BST Mode item to
BST
MANAGER
.
TEMP SENSOR P/N
24410