3.5 SETUP MENU
The
Setup
menu (Table 3-3) permits the operator to enter the unit password (159) which is
required to change the menu options. To prevent unauthorized use, the password will time-out
after 1 hour. Therefore, the correct password must be reentered when required. In addition to
permitting password entries, the
Setup
menu is also used to enter date and time, and units of
temperature measurements. A view-only software version display is also provided to indicate
the current Control Box software version.
Table 3-3: Setup Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1
Password
0
9999
0
2
Language
English
English
3
Time
12:00 am
11:59 pm
4
Date
01/01/00
12/31/99
5
Unit of Temp
Fahrenheit or Celsius
Fahrenheit
6
Comm Address
0
127
0
7
Baud Rate
2400, 4800, 9600, 19.2K
9600
8
OnAER Mode
Ethernet or SD Card
Ethernet
9
Min Upload Timer
0
9,999 Sec
0
10
Unit Alpha
E, G, H, R, N or A
A
11
Unit Year
0
99
0
12
Unit Serial #
0
9999
0
13
Software
Ver 0.00
Ver 9.99
Current software version
3.6 CONFIGURATION MENU
The
Configuration
menu shown in Table 3-4 permits adjustment of the Internal Setpoint (Setpt)
temperature regardless of whether the valid password has been entered. Setpt is required for
operation in the CONSTANT SETPOINT mode. The remaining options in this menu require the
valid password to be entered, prior to changing existing entries. This menu contains a number
of other configuration settings which may or may not be displayed, depending on the current
operating mode setting.
NOTE
The
Configuration
menu settings shown in Table 3-4 are Factory-
Set in accordance with the requirements specified for each
individual order. Therefore, under normal operating conditions, no
changes will be required.