Summary of Contents for 995 Series

Page 1: ...lding or plumbing codes may require modi ca tions to the information provided You are required to consult the local building and plumbing codes prior to installation If the information provided here i...

Page 2: ...at there is ade quate drainage Never pipe the discharge line directly into a drain age ditch sewer or sump Series 995 should never be installed where any part of the unit could become submerged in sta...

Page 3: ...eck valve and clean thoroughly NOTICE Periodic relief valve discharge may occur on dead end service applications such as boiler feed lines or cooling tower makeup lines due to fluctuating supply press...

Page 4: ...ng the white washer counter clockwise 6 To reassemble the relief valve press the seat firmly into place in the body snap the spring onto the relief valve stem cen ter the spring on the seat and insert...

Page 5: ...rst check assembly rotate the check module by hand counterclockwise 3 The second check assembly is removed by inserting the blade of a screwdriver into two opposing slots of the seat as shown in Figur...

Page 6: ...quipment and open No 2 shutoff valve of the device Test No 1 Check Valve No 2 Purpose To test check valve No 2 for tightness against reverse flow Requirements Valve must be tight against reverse flow...

Page 7: ...7 Notes...

Page 8: ...es delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no control This warranty shall be...