RP/IS-995

Installation, Maintenance, & Repair 
Series 995

Reduced Pressure Zone Backflow Preventers

Sizes: 

1

2

" through 2" (15-50mm)

NOTICE

For 

Australia

 and 

New Zealand

, line strainers should be installed 

between the upstream shutoff valve and the inlet of the backflow pre-
venter.

Testing

For field testing procedure, refer to Watts installation sheets  
IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on  
watts.com.

For other repair kits and service parts, refer to our Backflow 
Prevention Products Repair Kits & Service Parts price list  
PL-RP-BPD found on watts.com.

For technical assistance, contact your local Watts representative.

Watts 995 shown

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information 
can result in death, serious personal injury, property 
damage, or damage to the equipment.
Keep this Manual for future reference.

Local building or plumbing codes may require modifica-
tions to the information provided.  You are required to  
consult the local building and plumbing codes prior 
to installation.  If the information provided here is not 
consistent with local building or plumbing codes, the 
local codes should be followed.  This product must be 
installed by a licensed contractor in accordance with 
local codes and ordinances.

WARNING

!

Need for Periodic Inspection/Maintenance:

  This product 

must be tested periodically in compliance with local codes, 
but at least once per year or more as service conditions war-
rant.  If installed on a fire suppression system, all mechanical 
checks, such as alarms and backflow preventers, should be 
flow tested and inspected in accordance with NFPA 13 and/
or NFPA 25.  All products must be retested once maintenance 
has been performed.  Corrosive water conditions and/or 
unauthorized adjustments or repair could render the product 
ineffective for the service intended.  Regular checking and 
cleaning of the product’s internal components helps assure 
maximum life and proper product function.

WARNING

!

Summary of Contents for 995 Series

Page 1: ...lding or plumbing codes may require modi ca tions to the information provided You are required to consult the local building and plumbing codes prior to installation If the information provided here i...

Page 2: ...at there is ade quate drainage Never pipe the discharge line directly into a drain age ditch sewer or sump Series 995 should never be installed where any part of the unit could become submerged in sta...

Page 3: ...eck valve and clean thoroughly NOTICE Periodic relief valve discharge may occur on dead end service applications such as boiler feed lines or cooling tower makeup lines due to fluctuating supply press...

Page 4: ...ng the white washer counter clockwise 6 To reassemble the relief valve press the seat firmly into place in the body snap the spring onto the relief valve stem cen ter the spring on the seat and insert...

Page 5: ...rst check assembly rotate the check module by hand counterclockwise 3 The second check assembly is removed by inserting the blade of a screwdriver into two opposing slots of the seat as shown in Figur...

Page 6: ...quipment and open No 2 shutoff valve of the device Test No 1 Check Valve No 2 Purpose To test check valve No 2 for tightness against reverse flow Requirements Valve must be tight against reverse flow...

Page 7: ...7 Notes...

Page 8: ...es delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no control This warranty shall be...

Reviews: