General operating notes
Page 32 / 52
In order to test the inverter, follow the procedure described below:
1) Turn on power supply to the inverter. The power LED on the digital operator will light up.
2) Set
function
A 02
to 02.
3) Set function
A 01
to 00. Now the inverter can be operated using the built in potentiometer
which is indicated by the lit lamp above the potentiometer.
4) After pressing the RUN key the motor starts to run and the RUN lamp lights up.
5) The actual frequency can be monitored using function
d 01
.
6) You can stop the test run by pressing the STOP key.
CAUTION After the test run has been completed, check the following items to ensure that
the motor will not be damaged:
Was the direction of the motor run correct? Was there any trip condition during
acceleration or deceleration? Were there any unusual motor sounds or
vibrations?
When a trip occured during the test run due to overcurrent or overvoltage,
increase acceleration or deceleration time.