Control wiring
Never apply mains power to the D-connectors. Apply the correct signals to
the pins shown. Limit signals to the maximum values shown. Do not apply
voltage across other pins. Permanent damage, not covered by warranty, may
result.
Keep 4-20 mA and low voltage signals separate from mains power. Use
separate glanded input cables. Following best EMC practice and use of
shielded glands is recommended.
Ensure that multi-strand wires are terminated with a crimp suitable to the
wire diameter, (applies to NEMA or SCADA model connections only, not sub-D
connector type terminations). Failure to do so may result in electric shock.
13.1
Upper D-connector
Recommended control cable: 7/0.2 mm 24AWG screened. Cable screen should be earthed with a 360
deg connection to a conductive back-shell. This will be connected to pump mains EARTH via the D
connector body. Mains Earth is also available on pin 1 Upper D and pin 13 Lower D.
Functional
earth
Leak
Auto
man
Reserved
- do not
use
Reserved
- do not
use
Signal
ground
(0V)
VAUX
(+22.5V)
Commoning terminals,
used for voltage supply
for logic outputs
Signal
ground
(0V)
Logic
output
1
Logic
output
2
Logic
output
4
Logic
output
3
Upper D-connector
13.2
Lower D Connector
Functional
earth
Tacho mA
output
TTL
output 1
TTL
output 2
Dose
Direction
enable
Direction
Analogue 1
4-20mA
or 0-10V
Tacho
0-10V
Tacho
frequency
+10V
reference
Analogue 2
4-20mA or 0-10V
Signal
ground (0V)
Lower D-connector
Start
/stop
The 0 V of this pump is DC isolated (floating) from the pump mains Earth. However, do not allow pump
0 V to exceed 10 V from the pump mains earth through connection with remote equipment, to avoid
overstressing internal 0 V to Earth EMI capacitors.
22
m-630dun-en-08.2