Warning Codes

In the event of a warning, the inverter display will flash. The last warning to occur is stored in parameter P931.

Warning

Cause

Corrective action

002

Current limit active

Check whether the motor power corresponds to the inverter power.
Check that the cable length limits have not been exceeded.
Check motor cable and motor for short-circuits and earth faults.
Check whether the motor parameters (P080-P085) correspond with the motor
being used.
Check the stator resistance (P089).
Increase the ramp start up time (P002).
Reduce the boost set in P078 and P079.
Check whether the motor is obstructed or overloaded.

003

Voltage slip active

004

Slip limit exceeded.

005

Inverter overtemperature

Check that the ambient temperature is not too high.

(heatsink)

Check that the air inlet and outlet are not obstructed.
Check that the inters integral fan is working.

006

Motor over-temperature

Check if motor is overloaded.
Check that P087 has not been set to 1 without a PTC being connected.

010

Use power supply- current limit

018

Auto re-start after fault (P018)
is pending

WARNING: The inverter may start at any time.

075

Braking resistor-hot

System Parameters

Note: In the following parameter table:

l

Indicates parameters that can be changed during operation.

¶¶¶

Indicates that the value of this factory setting depends on the rating of the inverter.

If parameters are changed accidentally, all parameters can be reset to their default values by setting parameter P944 to 1 and
then pressing P.

Parameter Function

Default

Your setting

P001

Operating dis[lay

-

P001 

l

Dis[lay mode

0

P002 

l

Ramp up time (seconds)

10.00

P003 

l

Ramp down time (seconds)

25.00

P004 

l

Smoothing (seconds)

0.0

P005 

l

Digital frequency setpoint (Hz)

50.00

P006

Frequency setpoint source selection

1

P007

Keypad control

0

P009 

l

Parameter protection setting

0

P011

Frequency setpoint memory

0

P012 

l

Minimum motor frequency (Hz)

0.00

P013 

l

Maximum motor frequency (Hz)

50.00

P014 

l

Skip frequency 1 (Hz)

0.00

P015 

l

Automatic restart after mains failure

0

P016 

l

Start on the fly

0

P017 

l

Smoothing type

1

P018 

l

Automatic restart after fault

0

P019 

l

Skip frequency bandwidth (Hz)

2.00

P020

Flying start ramp time (seconds)

25.0

P021 

l

Minimum analogue frequency (Hz)

0.00

P022 

l

Maximum analogue frequency (Hz)

50.00

P051

Selection control function (DIN1 - terminal 5) fixed

1

frequency 3 or binary fixed frequency bit 0

P052

Selection control function (DIN2 - terminal 6) fixed

2

frequency 2 or binary fixed frequency bit 1

Summary of Contents for 621 Trio

Page 1: ...621 Trio 621tr gb 02 pdf...

Page 2: ...ted to malicious or accidental damage or electrical surge are excluded Warranties purporting to be on behalf of Watson Marlow Limited made by any person including representatives of Watson Marlow Limi...

Page 3: ...power off and wait one minute so that the dc link capacitors can discharge Some parameter settings can start the motor automatically after a mains failure The Trio inverter is not to be used as an eme...

Page 4: ...htening torques are used Access cover retaining screws 2 5Nm Gland hole covers 1 0Nm Mains connector screws 1 0Nm Control connector PL700 0 4Nm Check the supply voltage is correct for the inverter use...

Page 5: ...link from DIN1 pin 5 and P10 pin 1 to DIN2 pin 6 and P10 pin 1 on the control cable connector see Figs 2 and 3 b Apply mains power The green and yellow LEDs will illuminate to show that power is appl...

Page 6: ...r direction 5 F current S setpoint frequency 6 Motor rpm 7 Motor voltage 8 Motor torque max Other OPm2 functions The parameter settings required can be entered using the three buttons P I and J on the...

Page 7: ...e on off switch This sets up the inverter for clockwise rotation default If counter clockwise operation is required connect a switch between control terminals 6 and 1 d Connect the OPm2 and set parame...

Page 8: ...ault Switch off power and switch on again F012 External trip PTC Check if motor is overloaded F013 Programme fault Switch off power and switch on again F018 Auto restart after fault Automatic re start...

Page 9: ...resistor hot System Parameters Note In the following parameter table l Indicates parameters that can be changed during operation Indicates that the value of this factory setting depends on the rating...

Page 10: ...power for motor kW hp P086 l Motor current limit 150 P087 Motor PTC enable 0 P088 Automatic calibration 0 1 P089 l Stator resistance W P091 l Serial link slave address 0 P092 l Serial link baud rate 6...

Page 11: ...ate for each pump returned RGA No 1 Company Address Postcode Telephone Fax Number 3 4 Cleaning fluid to be used if residue of chemical is found during 2 Product servicing 2 1 Serial Number a 2 2 Has t...

Reviews: