background image

7

4. Using external analogue control

(a)

Remove the four M5 cross-head screws on the inverter’s cover to access the electrical terminals (see Fig.2).

(b)

Connect a 4.7 kW potentiometer to the control terminals as shown in Fig. 3 or apply a 0 - 10 V signal between pin 2 (0V) and
pin 3 (AIN+). In both cases, position jumper JP304 to connect 0V to AIN-.

(c)

Ensure that a link is fitted between pin 5 (DIN1) and pin 1 (P10+).

(d)

Check that voltage input is selected by ensuring that the jumper is fitted to JP301 (Fig 2).

(e)

Refit the cover, tighten the cover screws to the correct torque and then apply mains power to the inverter.

(f)

Turn the external potentiometer (or adjust the analogue control voltage) until the desired frequency is achieved. The unit
will not switch on until a minimum of 2 V has been applied.

(g)

Turning the potentiometer counter-clockwise or adjusting the analogue control voltage below 2 V will slow the motor to a
stop.

Note:

The frequency set by the external voltage is added to the frequency set by the internal potentiometer. A run/stop switch can
be used to start and stop the motor, or the direction of rotation can be changed by connecting the link to DIN2 instead of
DIN1.

5. Remote control using pre-set frequencies

For basic startup configuration, proceed as follows:

(a)

Remove the four M5 cross head screws on the inverter’s cover to access the electrical terminals (see Fig. 2 and 3).

(b)

Remove the link between pin 5 (DIN1) and pin 1 (P10+).

(c)

Connect pin 5 (DIN1) pin 1 (P10+) via a simple on/off switch. This sets up the inverter for clockwise rotation (default). If
counter-clockwise operation is required, connect a switch between control terminals 6 and 1.

(d)

Connect the OPm2 and set parameter P005 to the desired frequency setpoint.

(e)

Set parameter P006 to 000 to specify digital setpoint.

(f)

Set the external on/off switch to on. The inverter will now run at the frequency set by P005.

6. Remote control using RS485

Up to 31 Trios can be controlled via a 2-wire bi-directional RS485 serial link connected to the control terminals (see Fig 2 and
3), or the OPm2 socket on the side of the Trio. Baud rate 1200 to 19200 (set by parameter P092), serial line time-out 0-240
seconds (parameter P093).

Safety

Minimum speed running

The minimum safe speed to run the TRIO is 5Hz.

Fault  finding

If the motor does not start up check the LEDs on the side of the inverter:

LED State

TRIO Status

Green

Yellow

ON

ON

Mains power on, inverter not running (STANDBY)

ON

OFF

Inverter running, as control commands (ON)

Flashing

Flashing

Current limit warning

Flashing

ON

Inverter over temperature

ON

Flashing

Motor over temperature

OFF

ON

Other fault (e.g. tripped)

OFF

Flashing

Mains under voltage

OFF

OFF

Mains supply fault (e.g. faulty external switch)

If a fault occurs: switch off, disconnect and then reconnect the power, and then switch on again. Switch off if the fault condition
persists. Trips can be reset by connecting a switch to DIN3 (Fig. 2 and 3).

If a warning occurs: switch off, disconnect and reconnect the power and then switch on again. If the fault/warning persists, further
investigation requires an OPm2 or a serial link connection.

If the OPm2 display shows a fault code, refer to Fault Codes.

Summary of Contents for 621 Trio

Page 1: ...621 Trio 621tr gb 02 pdf...

Page 2: ...ted to malicious or accidental damage or electrical surge are excluded Warranties purporting to be on behalf of Watson Marlow Limited made by any person including representatives of Watson Marlow Limi...

Page 3: ...power off and wait one minute so that the dc link capacitors can discharge Some parameter settings can start the motor automatically after a mains failure The Trio inverter is not to be used as an eme...

Page 4: ...htening torques are used Access cover retaining screws 2 5Nm Gland hole covers 1 0Nm Mains connector screws 1 0Nm Control connector PL700 0 4Nm Check the supply voltage is correct for the inverter use...

Page 5: ...link from DIN1 pin 5 and P10 pin 1 to DIN2 pin 6 and P10 pin 1 on the control cable connector see Figs 2 and 3 b Apply mains power The green and yellow LEDs will illuminate to show that power is appl...

Page 6: ...r direction 5 F current S setpoint frequency 6 Motor rpm 7 Motor voltage 8 Motor torque max Other OPm2 functions The parameter settings required can be entered using the three buttons P I and J on the...

Page 7: ...e on off switch This sets up the inverter for clockwise rotation default If counter clockwise operation is required connect a switch between control terminals 6 and 1 d Connect the OPm2 and set parame...

Page 8: ...ault Switch off power and switch on again F012 External trip PTC Check if motor is overloaded F013 Programme fault Switch off power and switch on again F018 Auto restart after fault Automatic re start...

Page 9: ...resistor hot System Parameters Note In the following parameter table l Indicates parameters that can be changed during operation Indicates that the value of this factory setting depends on the rating...

Page 10: ...power for motor kW hp P086 l Motor current limit 150 P087 Motor PTC enable 0 P088 Automatic calibration 0 1 P089 l Stator resistance W P091 l Serial link slave address 0 P092 l Serial link baud rate 6...

Page 11: ...ate for each pump returned RGA No 1 Company Address Postcode Telephone Fax Number 3 4 Cleaning fluid to be used if residue of chemical is found during 2 Product servicing 2 1 Serial Number a 2 2 Has t...

Reviews: