Mains cable connections

Ensure that the power source supplies the correct voltage and is designed for the rated current. Use a circuit-breaker with a 10A
current rating between the power supply and Trio. Use Class 1 60/75°C copper wire only with a cross sectional area of 1mm. If
crimp terminals are used they must be insulated. If crimps are not used, the strip length must not exceed 5mm. Feed the power
cable into the inverter via the gland hole nearest to the motor shaft using a PG16 gland. Connect the power leads to terminals L1,
L2 and the separate earth. Use a 4-5mm cross head screwdriver to tighten the terminal screws.

1 Mains connector

2 OPM2 Hand Held controller connector

3 Control terminal 1

4 Control terminal 12

5 JP305 - JP302

6 JP300 - JP301

7 LED (green)

8 LED (yellow)

9 Internal Potentiometer R314

Fig 2. Electrical connection drawing

Ensure that the following tightening torques are used: Access cover retaining screws:
2.5Nm, Gland hole covers: 1.0Nm, Mains connector screws: 1.0Nm, Control connector PL700: 0.4Nm.
Check the supply voltage is correct for the inverter used by referring to the rating label.

Control cable connections

The control and power supply cables (max 1mm diameter) must be laid separately. They must not be fed
through the same cable conduit/ trunking.

Use screened cable for the control lead.

Feed the control cable into the inverter via the appropriate gland hole (see Fig. 2). Connect the control wires in accordance with the
information in Fig. 3 and 4 (also see Fig. 1).

IMPORTANT:

A wire link will have been factory fitted between control terminals 5 (DIN1) and 1 (P10+) to enable the Trio to
operate when control potentiometer R314 is used. The wire link must be removed when operation via a run/
stop switch is required.

Note that the optional potentiometer fitted as an analogue set point shown in Fig. 3 assumes that jumper JP304 is connecting 0V
(pin 2) to AIN- (pin 4). Also, P15+ can be used as an alternative to P10+ for the digital inputs.

Summary of Contents for 621 Trio

Page 1: ...621 Trio 621tr gb 02 pdf...

Page 2: ...ted to malicious or accidental damage or electrical surge are excluded Warranties purporting to be on behalf of Watson Marlow Limited made by any person including representatives of Watson Marlow Limi...

Page 3: ...power off and wait one minute so that the dc link capacitors can discharge Some parameter settings can start the motor automatically after a mains failure The Trio inverter is not to be used as an eme...

Page 4: ...htening torques are used Access cover retaining screws 2 5Nm Gland hole covers 1 0Nm Mains connector screws 1 0Nm Control connector PL700 0 4Nm Check the supply voltage is correct for the inverter use...

Page 5: ...link from DIN1 pin 5 and P10 pin 1 to DIN2 pin 6 and P10 pin 1 on the control cable connector see Figs 2 and 3 b Apply mains power The green and yellow LEDs will illuminate to show that power is appl...

Page 6: ...r direction 5 F current S setpoint frequency 6 Motor rpm 7 Motor voltage 8 Motor torque max Other OPm2 functions The parameter settings required can be entered using the three buttons P I and J on the...

Page 7: ...e on off switch This sets up the inverter for clockwise rotation default If counter clockwise operation is required connect a switch between control terminals 6 and 1 d Connect the OPm2 and set parame...

Page 8: ...ault Switch off power and switch on again F012 External trip PTC Check if motor is overloaded F013 Programme fault Switch off power and switch on again F018 Auto restart after fault Automatic re start...

Page 9: ...resistor hot System Parameters Note In the following parameter table l Indicates parameters that can be changed during operation Indicates that the value of this factory setting depends on the rating...

Page 10: ...power for motor kW hp P086 l Motor current limit 150 P087 Motor PTC enable 0 P088 Automatic calibration 0 1 P089 l Stator resistance W P091 l Serial link slave address 0 P092 l Serial link baud rate 6...

Page 11: ...ate for each pump returned RGA No 1 Company Address Postcode Telephone Fax Number 3 4 Cleaning fluid to be used if residue of chemical is found during 2 Product servicing 2 1 Serial Number a 2 2 Has t...

Reviews: