Version 1.0
PN: 2042-8198
Page 62 of 75
DN: 10-32813
Volume
Volume is a new object. It is used to obtain information about each of the three volumes. This
information is only updated upon request by way of the Refresh member.
IMPORTANT: Use caution with the Format member. All data on this volume will be lost upon execution
of this command!
Volume 102 (0x66), Instances 1-3
Member ID
Member Name
Data Type
Access
NV
Min
Max
Default
Comments / Description
1
0x01
Name
STRING
R
1: "sd:"
2: "nor:"
3: "ram:"
Volume name
2
0x02
Label
STRING
RW
F
0
11
1: "MICRO SD"
2: "NOR FLASH"
3: "RAM DISK"
Volume label
3
0x03
File System
STRING
R
File system
4
0x04
Used Space
UINT32
R
Used space (bytes)
5
0x05
Free Space
UINT32
R
Free space (bytes)
6
0x06
Capacity
UINT32
R
Capacity (bytes)
7
0x07
Percent Used
FLOAT
R
Used space (%)
8
0x08
Percent Free
FLOAT
R
Free space (%)
11
0x0B
State
ENUM16
R
2211: Disconnected
1782: Start
1662: Ready
1638: Stop
2212: Stopped
12
0x0C
Error
UINT16
R
Last error
16
0x10
Refresh
ENUM16
RW
59
59: No
106: Yes
17
0x11
Start / Stop
ENUM16
RW
59
59: No
106: Yes
18
0x12
Format
ENUM16
RW
59
59: No
106: Yes
Optic Sensing
This feature is only available if the model number is RMAP-
8
AXX-XXXX.
Optic sensing objects are used to configure and report status of the inputs in an adjacent fiber optic
module.
Optic Sensing 210 (0xD2), Instances 1-4
Member ID
Member Name
Data Type
Access
NV
Min
Max
Default
Comments / Description
1
0x01
Temperature
FLOAT
R
2
0x02
Status
UINT16
R
0
7
1: Probe connected, no fault conditions
2: Probe disconnected, Probe recovery mode
3: Probe connected, Max LED current
4: Probe connected, low light level
6: No signal, possible LED Failure
7: LED current above warning alarm
3
0x03
LED Current (mA)
FLOAT
R
0
20
4
0x04
LED Counts
UINT16
R
5
0x05
Decay Time (µs)
FLOAT
R
8
0x08
Probe Type
UINT8
RW
F
1
4
1
Class variable
9
0x09
PCB Temperature
FLOAT
R
10
0x0A
LED Warning Point (mA)
FLOAT
RW
F
0
20
15
Class variable
Summary of Contents for RMA PLUS RMAP-2A Series
Page 1: ...Version 1 0 PN 2042 8198 Page 1 of 75 DN 10 32813 RMA PLUS User Manual...
Page 8: ...Version 1 0 PN 2042 8198 Page 8 of 75 DN 10 32813...
Page 11: ...Version 1 0 PN 2042 8198 Page 11 of 75 DN 10 32813 Figure 3 Ground Wire Location...
Page 26: ...Version 1 0 PN 2042 8198 Page 26 of 75 DN 10 32813 Figure 22 RMA PLUS via USBD MICRO SD root...
Page 27: ...Version 1 0 PN 2042 8198 Page 27 of 75 DN 10 32813 Figure 23 RMA PLUS via USBD NOR FLASH root...
Page 42: ...Version 1 0 PN 2042 8198 Page 42 of 75 DN 10 32813 Figure 37 Default web page Index html...
Page 75: ...Version 1 0 PN 2042 8198 Page 75 of 75 DN 10 32813...