Power Series Output Rating Curves
Natural Convection
All curves are at 100% on and with 90°C rated load wire and line wire connected. Note that each chart is
slightly different on the amperage scale. The safe operating region is from 1 amp up to the specific curve for
the output amperage code selected. For example: N25 Single Phase is rated up to 140 amps at 50°C; N30
Single Phase is rated for 165 amps at 50°C.
3 Phase, 3-Leg and 3-Zone Multizone
Natural Convection at 100% On
25
30
35
40
45
50
55
60
65
Current (Amps) into a Resistive Load
N20
N25
N30
Enclosure Internal
Ambient Temperature
°
C
60
140
70
80
90
100
110
120
130
50
3 Phase, 2-Leg and 2-Zone Multizone
Natural Convection at 100% On
25
30
35
40
45
50
55
60
65
Current (Amps) into a Resistive Load
60
140
70
80
90
100
110
120
130
N20
N25
N30
Enclosure Internal
Ambient Temperature
°
C
Single Phase Natural Convection at 100% On
25
30
35
40
45
50
55
60
65
Current (Amps) into a Resistive Load
80
210
90
100 110 120 130 140 150
170 180 190 200
160
N20
N25
N30
Enclosure Internal
Ambient Temperature
°
C
2 . 6
■
I n s t a l l a t i o n
Wa t l o w P o w e r S e r i e s
Summary of Contents for PC1X-N20
Page 4: ...ii Watlow Power Series Table of Contents...
Page 72: ......