Active if
[glbl]
is set to
[`Off]
.
863 r/w
[`std]
active (0)
[`std]
active (0)
[`LaT]
latched (1)
[`SIl]
silenced (2)
[LaSI]
latched and
silenced (3)
[Line]
Line Loss Alarm
Configuration
Selects the line loss
alarm configuration.
Active: Always.
Output will de-energize at this
heatsink shut down tempera-
ture (degrees C). The default
maximum temperature is
model number dependent.
990 r/w
Value equal to
[`sdÇ]
or
less. User
adjustable.
See Factory
Menu for
actual safety
shutdown
temp.
[```0]
to
[`sdÇ]
[alÇ`]
Heat Sink Over
Temperature Alarm
Temperature
Select heat sink
overtemp alarm
configuration.
Active if
[glbl]
is set to
[`Off]
.
862 r/w
[`std]
active (0)
[`std]
active (0)
[`LaT]
latched (1)
[`SIl]
silenced (2)
[LaSI]
latched and
silenced (3)
[``OT]
Heat Sink Over
Temperature
Alarm Config.
Select over tempera-
ture alarm configu-
ration.
Active if heater diagnostics is
installed.
Active if
[glbl]
is set to
[`Off]
.
861 r/w
[`std]
active (0)
[`std]
active (0)
[`LaT]
latched (1)
[`SIl]
silenced (2)
[LaSI]
latched and
silenced (3)
[`tol]
Heater Tolerance
Alarm Config.
Selects heater
tolerance alarm
configuration.
Active if heater diagnostics is
installed.
Active if
[glbl]
is set to
[`Off]
.
860 r/w
[`std]
active (0)
[`std]
active (0)
[`LaT]
latched (1)
[`SIl]
silenced (2)
[LaSI]
latched and
silenced (3)
[Open]
Heater Open
Alarm Config.
Select heater open
alarm configuration.
Active: Always.
851 r/w
[`std]
all
alarms
active (0)
[`std]
all alarms
active (0)
[`LaT]
latched (1)
[`SIl]
silenced (2)
[LaSI]
latched and
silenced (3)
[`Off]
off (4)
[glbl]
Global Alarm
Configuration
Selects global alarm
configuration. Config-
ures all alarms to the
same type or if set to
OFF allows individual
alarm configuration.
Active: Always.
850 r/w
[al`O]
de-
energized
on alarm
(1)
[al`C]
energized on
alarm (0)
[al`O]
de-energized
on alarm (1)
[a|lgc]
Active Relay State
Select the relay
state on an alarm
condition.
[`Alr]
Setup Alarms Configuration Menu
[`Set]
Setup Page
This menu is used to set up the alarm configuration. For a definition of the alarm types —
standard, latched, silenced, latched and silenced, see page 5.7.
6 . 1 0
■
Wa t l o w P o w e r S e r i e s
P a r a m e t e r s , C h a p t e r 6
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Address
Parameters to Appear
read/write