w
write any value
330
Clear Error Input 2, Key Press Simulation
w
write any value
349
Clear Error Input 3, Key Press Simulation
w
write any value
5566
Clear Input 1 Offsets, Analog Input 1
r/w
0
No
1
Yes
5567
Clear Input 2 Offsets, Analog Input 2
r/w
0
No
1
Yes
5568
Clear Input 3 Offsets, Analog Input 3
r/w
0
No
1
Yes
1315
Clear Locks, Set Lockout
w
0
Yes
1061
Condition, Digital Input 1
r/w
0
Low
1
High
1063
Condition, Digital Input 2
r/w
0
Low
1
High
1065
Condition, Digital Input 3
r/w
0
Low
1
High
1067
Condition, Digital Input 4
r/w
0
Low
1
High
298
Control Set Point
r
1140
Control Type, Analog Input 2
r/w
0
Normal
3
Remote
4
Alternate
1141
Control Type, Analog Input 3
r/w
0
Normal
1
Ratio
2
Differential
3
Remote
5
Cascade
1400-15
Custom Main Page Parameters (P1 to P16)
r/w
0
None
1
Input 1
2
Input 1 Value Bar
3
Input 2
4
Input 2 Value Bar
5
Input 3
6
Input 3 Value Bar
7
Digital Set Point
8
Digital Differential Value
9
Differential Set Point
10 Set Differential
11 Digital Ratio Value
12 Ratio Set Point
13 Set Ratio
14 Remote Set Point 2
15 Remote Set Point 3
16 Target Set Point
17 Inner Set Point
18 Set Point 1
19 Set Point 1 Bar
20 % Power 1A
21 % Power 1B
22 % Power 1A Bar
23 % Power 1B Bar
24 Tune Status 1
25 Digital Inputs
26 Active Ch1 PID Set
509
Cycle Time Type, Control Output 1A
r/w
0
Variable Burst
1
Fixed Time
559
Cycle Time Type, Control Output 1B
r/w
0
Variable Burst
1
Fixed Time
506
Cycle Time, Control Output 1A
r/w
1 to 600 in tenths
556
Cycle Time, Control Output 1B
r/w
1 to 600 in tenths
2605
Dead Band 1A, Cascade PID Set 1
r/w
0 to 30000
2625
Dead Band 1A, Cascade PID Set 2
r/w
0 to 30000
2645
Dead Band 1A, Cascade PID Set 3
r/w
0 to 30000
2665
Dead Band 1A, Cascade PID Set 4
r/w
0 to 30000
2685
Dead Band 1A, Cascade PID Set 5
r/w
0 to 30000
505
Dead Band 1A, PID Set 1
r/w
0 to 30000
515
Dead Band 1A, PID Set 2
r/w
0 to 30000
525
Dead Band 1A, PID Set 3
r/w
0 to 30000
535
Dead Band 1A, PID Set 4
r/w
0 to 30000
545
Dead Band 1A, PID Set 5
r/w
0 to 30000
2615
Dead Band 1B, Cascade PID Set 1
r/w
0 to 30000
2635
Dead Band 1B, Cascade PID Set 2
r/w
0 to 30000
2655
Dead Band 1B, Cascade PID Set 3
r/w
0 to 30000
2675
Dead Band 1B, Cascade PID Set 4
r/w
0 to 30000
2695
Dead Band 1B, Cascade PID Set 5
r/w
0 to 30000
555
Dead Band 1B, PID Set 1
r/w
0 to 30000
565
Dead Band 1B, PID Set 2
r/w
0 to 30000
575
Dead Band 1B, PID Set 3
r/w
0 to 30000
585
Dead Band 1B, PID Set 4
r/w
0 to 30000
595
Dead Band 1B, PID Set 5
r/w
0 to 30000
606
Decimal, Analog Input 1
r/w
0
0
1
0.0
2
0.00 (process)
3
0.000 (process)
616
Decimal, Analog Input 2
r/w
0
0
1
0.0
2
0.00 (process)
3
0.000 (process)
626
Decimal, Analog Input 3
r/w
0
0
1
0.0
2
0.00 (process)
3
0.000 (process)
2603
Derivative 1A, Cascade PID Set 1
r/w
0 to 999 minutes (in hundredths)
2623
Derivative 1A, Cascade PID Set 2
r/w
0 to 999 minutes (in hundredths)
2643
Derivative 1A, Cascade PID Set 3
r/w
0 to 999 minutes (in hundredths)
2663
Derivative 1A, Cascade PID Set 4
r/w
0 to 999 minutes (in hundredths)
2683
Derivative 1A, Cascade PID Set 5
r/w
0 to 999 minutes (in hundredths)
9 . 4
■
C o m m u n i c a t i o n s
Wa t l o w S e r i e s F 4 P
Summary of Contents for F4P Series
Page 4: ...ii Table of Contents Watlow Series F4P Notes...
Page 14: ...2 8 Operating from the Front Panel Watlow Series F4P Notes...
Page 58: ...6 32 Parameters Watlow Series F4P Notes...
Page 77: ...Watlow Series F4P Features 7 19 Notes...
Page 78: ...7 20 Features Watlow Series F4P Notes...
Page 94: ...8 16 Installation and Wiring Watlow Series F4P Notes...