6 . 3 0
■
P a r a m e t e r s
Wa t l o w S e r i e s F 4 P
✔
Note: Press the Information Key
ˆ
for more task-related
tips.
*The tenth digit of your model number,
F4PX-XXXX-X
X
XX
,
determines what RTD calibration resistance values the unit
uses. Refer to the Ordering Information in the Appendix.
Options 1-4, 100
Ω
RTD - 15.00 and 380.00
Ω
Options 5-8, 500
Ω
or 1000
Ω
RTD - 240.00 and 6080.00
Ω
Factory Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
(I/O, Set)
Parameters to Appear
Active: Always.
Output
1605 [1A]
1610 [1B]
Rexmit
1625 [1]
1630 [2]
r/w
20.000mA
0.000 to 24.000mA
(0 to 24000)
20.000mA
Store 20mA calibration
for the process output.
Active: Always.
Output
1604 [1A]
1609 [1B]
Rexmit
1624 [1]
1629 [2]
r/w
4.000mA
0.000mA to 6.000mA
(0 to 6000)
4.000mA
Store 4mA calibration for
the process output.
Main > Factory > Calibration > Calibrate Output x (1A or 1B) and Retransmit x (1 and 2)
Calibrate Output x (1A or 1B) and Retransmit x (1 and 2)
Active: Always.
Inputs 3 appear only if the con-
troller is the enhanced version
(F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (13)
1000 Ohms
Store 1000.00
Ω
calibra-
tion for the slidewire
input.
Active: Always.
Inputs 3 appear only if the con-
troller is the enhanced version
(F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (12)
15.0 Ohms
Store 15.00
Ω
calibration
for the slidewire input.
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (11)
20.000mA
Store 20mA calibration
for the process input.
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (10)
4.000mA
Store 4mA calibration for
the process input.
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (9)
10.000V
Store 10.000V calibration
for the process input.
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (8)
0.000V
Store 0.000V calibration
for the process input.
Active: Always.
Input
1603 [1]
1608 [2]
1613 [3]
w
Yes (7)
6080.0 Ohms*
Store 6080.00
Ω
calibra-
tion for the 500
Ω
or 1k
Ω
RTD input.
Summary of Contents for F4P Series
Page 4: ...ii Table of Contents Watlow Series F4P Notes...
Page 14: ...2 8 Operating from the Front Panel Watlow Series F4P Notes...
Page 58: ...6 32 Parameters Watlow Series F4P Notes...
Page 77: ...Watlow Series F4P Features 7 19 Notes...
Page 78: ...7 20 Features Watlow Series F4P Notes...
Page 94: ...8 16 Installation and Wiring Watlow Series F4P Notes...