Wa t l o w S e r i e s F 4 P
P a r a m e t e r s
■
6 . 5
✔
Note: For more information about how parameter set-
tings affect the controller’s operation, see the Features
Chapter.
* None of the B parameters are active if both outputs are
set to cool or heat.
Operations Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
(I/O, Set)
Parameters to Appear
Active if Control Type (Analog
Input 3) is set to Cascade, PID
Units (Setup Page) is set to SI
and Proportional Band is not
set to 0.*
1A
1B
Set
2601 2611 [1]
2621 2631 [2]
2641 2651 [3]
2661 2671 [4]
2681 2691 [5]
r/w
0 minutes
0.00 to 99.99 minutes
(0 to 9999)
Integral x (A or B)
Set the integral time in
minutes.
[or]
Active if Control Type (Analog
Input 3) is set to Cascade.*
1A
1B
Set
2600 2610 [1]
2620 2630 [2]
2640 2650 [3]
2660 2670 [4]
2680 2690 [5]
r/w
25°F
14°C
0 to 30000
0.0 to 3000.0
0.00 to 300.00
0.000 to 30.000
(0 to 30000) in integer,
tenths, hundredths or
thousandths
Proportional Band x (A or
B)
Define the proportional
band for PID control.
Main > Operations > Edit PID > Cascade Outer Loop PID Set X (1 to 5)
Cascade Outer Loop PID Set x (1 to 5)
* None of the B parameters are active if both outputs are set to cool or heat.
Active if Proportional Band is set
to 0 and one output is set to
heat and the other to cool
(Setup Page).* Based on dial
setting.
1A
1B
Set
507
557
[1]
517
567
[2]
527
577
[3]
537
587
[4]
547
597
[5]
r/w
3
0 to 30000
0.0 to 3000.0
0.00 to 300.00
0.000 to 30.000
(0 to 30000) in integer,
tenths, hundredths or
thousandths
Hysteresis x (A or B)
Define the process vari-
able change from the set
point required to re-en-
ergize the output (in on-
off mode).
Active if Proportional Band is not
set to 0 and one output is set to
heat and the other to cool
(Setup Page).* Based on decimal
setting.
1A
1B
Set
505
555
[1]
515
565
[2]
525
575
[3]
535
585
[4]
545
595
[5]
r/w
0
0 to 30000
0.0 to 3000.0
0.00 to 300.00
0.000 to 30.000
(0 to 30000) in integer,
tenths, hundredths or
thousandths
Dead Band x (A or B)
Define the effective shift
in the heating and cool-
ing set points to prevent
conflict.
Active if PID Units (Setup Page)
is set to U.S. and Proportional
Band is not set to 0.*
1A
1B
Set
504
554
[1]
514
564
[2]
524
574
[3]
534
584
[4]
544
594
[5]
r/w
0.00 minutes
0.00 to 9.99 minutes
(0 to 999)
Rate x (A or B)
Set the rate time.
Active if PID Units (Setup Page)
is set to SI and Proportional
Band is not set to 0.*
1A
1B
Set
503
553
[1]
513
563
[2]
523
573
[3]
533
583
[4]
543
593
[5]
r/w
0.00 minutes
0.00 to 9.99 minutes
(0 to 999)
Derivative x (A or B)
Set the derivative time.
Active if PID Units (Setup Page)
is set to U.S. and Proportional
Band is not set to 0.*
1A
1B
Set
502
552
[1]
512
562
[2]
522
572
[3]
532
582
[4]
542
592
[5]
r/w
0 per minute
0.00 per minute to
99.99 per minute
(0 to 9999)
Reset x (A or B)
Set the reset time in re-
peats per minute.
Active if PID Units (Setup Page)
is set to SI and Proportional
Band is not set to 0.*
1A
1B
Set
501
551
[1]
511
561
[2]
521
571
[3]
531
581
[4]
541
591
[5]
r/w
0 minutes
0.00 to 99.99 minutes
(0 to 9999)
Integral x (A or B)
Set the integral time in
minutes.
[or]
Summary of Contents for F4P Series
Page 4: ...ii Table of Contents Watlow Series F4P Notes...
Page 14: ...2 8 Operating from the Front Panel Watlow Series F4P Notes...
Page 58: ...6 32 Parameters Watlow Series F4P Notes...
Page 77: ...Watlow Series F4P Features 7 19 Notes...
Page 78: ...7 20 Features Watlow Series F4P Notes...
Page 94: ...8 16 Installation and Wiring Watlow Series F4P Notes...