Wa t l o w S e r i e s F 4 P
C o m m u n i c a t i o n s
■
9 . 7
581
Integral 1B, PID Set 4
r/w
0 to 9999 minutes in hundredths
591
Integral 1B, PID Set 5
r/w
0 to 9999 minutes in hundredths
704
Latching, Alarm Output 1
r/w
0
Alarm Self-clears
1
Alarm Latches
721
Latching, Alarm Output 2
r/w
0
Alarm Self-clears
1
Alarm Latches
1914
LED Intensity, Process Display
r/w
0 to 15
1515
Line Frequency, Diagnostic
r
xx
715
Low Power Limit, Control Output 1A
r/w
0% to High Limit-1
732
Low Power Limit, Control Output 1B
r/w
0% to High Limit-1
710
Low Scale, Retransmit Output 1
r/w
-19999 to 30000 (minimum sensor range)
727
Low Scale, Retransmit Output 2
r/w
-19999 to 30000 (minimum sensor range)
454
Manual to Auto Transfer, System
r/w
0
Restore Set Point
1
Reverse Bumpless
5
Manufacturing Date, Diagnostic
r
xxxx
453
Maximum Transfer Cool, System
r/w
-100% to 0%
452
Maximum Transfer Heat, System
r/w
0% to 100%
4501-17
Message 1 (Line 01, Char 01-17), Static Message r/w
4521-37
Message 1 (Line 02, Char 01-17), Static Message r/w
4541-57
Message 1 (Line 03, Char 01-17), Static Message r/w
4561-77
Message 1 (Line 04, Char 01-17), Static Message r/w
4581-97
Message 2 (Line 01, Char 01-17), Static Message r/w
4601-17
Message 2 (Line 02, Char 01-17), Static Message r/w
4621-37
Message 2 (Line 03, Char 01-17), Static Message r/w
4641-57
Message 2 (Line 04, Char 01-17), Static Message r/w
4661-77
Message 3 (Line 01, Char 01-17), Static Message r/w
4681-97
Message 3 (Line 02, Char 01-17), Static Message r/w
4701-17
Message 3 (Line 03, Char 01-17), Static Message r/w
4721-37
Message 3 (Line 04, Char 01-17), Static Message r/w
4741-57
Message 4 (Line 01, Char 01-17), Static Message r/w
4761-77
Message 4 (Line 02, Char 01-17), Static Message r/w
4781-97
Message 4 (Line 03, Char 01-17), Static Message r/w
4801-17
Message 4 (Line 04, Char 01-17), Static Message r/w
3060
Message Display Time, Digital Input 1
r/w
0 to 999
3061
Message Display Time, Digital Input 2
r/w
0 to 999
3062
Message Display Time, Digital Input 3
r/w
0 to 999
3063
Message Display Time, Digital Input 4
r/w
0 to 999
0
Model, Diagnostic
r
5280
4P
3200-09
Name (Char 01-10), Alarm Output 1
r/w
ASCII codes A to Z, 0 to 9, space
3210-19
Name (Char 01-10), Alarm Output 2
r/w
ASCII codes A to Z, 0 to 9, space
3000-06
Name (Char 01-07), Digital Input 1
r/w
ASCII codes A to Z, 0 to 9, space
3010-16
Name (Char 01-07), Digital Input 2
r/w
ASCII codes A to Z, 0 to 9, space
3020-26
Name (Char 01-07), Digital Input 3
r/w
ASCII codes A to Z, 0 to 9, space
3030-36
Name (Char 01-07), Digital Input 4
r/w
ASCII codes A to Z, 0 to 9, space
5506-15
Offset Point 01-10, Analog Input 1, rw
r/w
-19999 or Input Offset (x-1) Value
+ 1 to Input Offset (x+1) Value - 1 or 30000
5516-25
Offset Point 01-10, Analog Input 2, r/w
r/w
-19999 or Input Offset (x-1) Value
+ 1 to Input Offset (x+1) Value - 1 or 30000
5526-35
Offset Point 01-10, Analog Input 3, r/w
r/w
-19999 or Input Offset (x-1) Value
+ 1 to Input Offset (x+1) Value - 1 or 30000
5572
Offset Type, Analog Input 1
r/w
0
Single Linear
1
Multiple Point
5573
Offset Type, Analog Input 2
r/w
0
Single Linear
1
Multiple Point
5574
Offset Type, Analog Input 3
r/w
0
Single Linear
1
Multiple Point
5536-45
Offset Value 01-10, Analog Input 1
r/w
-1000 to 1000
5546-55
Offset Value 01-10, Analog Input 2
r/w
-1000 to 1000
5556-65
Offset Value 01-10, Analog Input 3
r/w
-1000 to 1000
904
Open Loop Detect, System
r/w
0
Off
1
On
1308
Operations, Alarm Set Point, Set Lockout
r/w
0
Full Access
1
Read Only
2
Password
3
Hidden
1306
Operations, Autotune PID, Set Lockoutr/w
r/w
0
Full Access
1
Read Only
2
Password
3
Hidden
1318
Operations, Control Set Point, Set Lockout
r/w
0
Full Access
1
Read Only
2
Password
3
Hidden
1307
Operations, Edit PID, Set Lockout
r/w
0
Full Access
1
Read Only
2
Password
3
Hidden
200
Operations Mode, Status
r/w
1
Auto Mode
2
Manual
1316
Operations, PID Crossover, Set Lockout
r/w
0
Full Access
1
Read Only
2
Password
3
Hidden
1317
Operations, Ramp Set Point, Set Lockout
r/w
0
Full Access
1
Read Only
2
Password
3
Hidden
1319
Operations, Remote Set Point, Set Lockout
r/w
0
Full Access
1
Read Only
2
Password
3
Hidden
16
Output 1A, Diagnostic
r
0
None
1
Mechanical Relay
2
SSR
3
DC
4
Process
Summary of Contents for F4P Series
Page 4: ...ii Table of Contents Watlow Series F4P Notes...
Page 14: ...2 8 Operating from the Front Panel Watlow Series F4P Notes...
Page 58: ...6 32 Parameters Watlow Series F4P Notes...
Page 77: ...Watlow Series F4P Features 7 19 Notes...
Page 78: ...7 20 Features Watlow Series F4P Notes...
Page 94: ...8 16 Installation and Wiring Watlow Series F4P Notes...