EZ-ZONE PM Limit Express
• 12 •
Install & Wiring
Power
Power
power
power
98
99
CF
CD
CE
Slot C
fuse
• 47 to 63 Hz
• 10VA maximum power consumption (PM3 and PM6)
• 14VA maximum power consumption (PM4, 8 and 9)
Low Power
• 12 to 40V
Î
(dc)
• 20 to 28V
Å
(ac) Semi Sig F47
High Power
• 85 to 264V
Å
(ac)
•100 to 240V
Å
(ac) Semi Sig F47
Ó
Warning:
Use National Electric (NEC) or other country-specific
standard wiring and safety practices when wiring and
connecting this controller to a power source and to
electrical sensors or peripheral devices. Failure to do
so may result in damage to equipment and property,
and/or injury or loss of life.
Note:
Maximum wire size termination and torque rating:
• 0.0507 to 3.30 mm2 (30 to 12 AWG) single-
wire termination or two 1.31 mm2 (16 AWG)
• 0.56 Nm (5.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled differently, de-
pending on the model number.
Note:
To prevent damage to the controller, do not connect
wires to unused terminals.