EZ-ZONE PM Limit Express
• 21 •
Setup Menu
Setup Menu
Display
Parameter Name Description
Range (
Defaults are shown
bold)
[
LoC]
[LoC]
Lockout Menu
Set the security clearance level. The user
can access the selected level and all lower
levels.
Appears if: Always
1 to 5
1 Operations Menu (read only)*
2 Operations Menu (Set point R/W)*
3 Operations Menu (Set point R/W, Control Mode R/W)*
4 Operations Menu R/W access)*
5 Operations Menu and Setup Menu full R/W access
*You can change the security level at any level
[Sen]
[ SEn]
Sensor Type
Set the analog sensor type to match the
device wired to this input.
Appears if: Always.
[``tC]
Thermocouple
[`MA]
Milliamps dc
[uolT]
Volts dc
[r0;1H]
RTD 100 Ω
[Lin]
[ Lin]
Linearization
Set the linearization to match the thermo-
couple type wired to this input.
For example, select
[```H]
for a type K
thermocouple.
Appears if: Sensor Type is set to Thermo-
couple.
[`b]
B
[`J]
J
[`t]
T
[`c]
C
[`H]
K
[`d]
D
[`n]
N
[`e]
E
[`r]
R
[`f]
F
[`S]
S
[``t;C]
[ t.C]
Thermistor Curve
Select a curve to apply to the thermistor
input.
[```A]
Curve A,
[```b]
Curve B,
[```C]
Curve C
[CUSt]
Custom
[``r;r]
[ r.r]
Resistance Range
Set the maximum resistance of the thermis-
tor input.
[```5]
5K,
[``10]
10K,
[``20]
20K,
[``40]
40K
[`dEC]
[ dEC]
Decimal
Set the precision of the displayed value.
Appears if: Always.
[```0]
Whole
[``0;0]
Tenths
[`0;00]
Hundredths
[`C_F]
[ C_F]
Display Units
Select which units will be displayed.
Appears if: Always.
[```F]
°F
[```C]
°C
[`r;Lo]
[ r.Lo]
Limit Set Point - Range Low
Sets the low limit of the set point adjustment
using a T/C and RTD; scales for process
inputs.
Appears if: Always.
-1,999.00 to 9,999.000 °F or Units
-1,110.555 to 5,555.000 °C
0.0