background image

F

1031, Section 2407

Page 5 of 8

Advantus

t

 Foam Pump Operation

Upon power up, the software revision number will be dis-

played. The unit will then display the flow rate.
Because the conductivity measurement for a given per-

centage mix changes with the flow rate, the calibration

data is stored in an array. The array holds entries for the

various parameters at several different flow rates that are

in between flow rates entered in the data array.

Figure 2. Operator Interface Terminal

IL2963

During normal operation, the OIT (Operation Interface Terminal) will display flow rate, percent mix, total water or total product.

SELECT

Selects data to display. The default is to display flow rate. Pressing the SELECT button will

scroll through the list, then wrap back around to the top of the list. The associated LED will

light to indicate what data is being displayed.

Flow Rate
Mix Percentage
Total Water
Total Product

Holding the SELECT button for more than two seconds will lock the display to the current

position. Pressing the SELECT button again will unlock.

UP ARROW

When the Mix Percentage is displayed, the current mix setpoint will be displayed. Sub-

sequent presses of the UP ARROW button will increase the Mix Setpoint by 0.1%. After a ten

second timeout, the display will return to the Flow Rate display.

DOWN ARROW

When the Mix Percentage is displayed, the current mix setpoint will be displayed. Sub-

sequent presses of the DOWN ARROW button will decrease the Mix Setpoint by 0.1%. After

a ten second timeout, the display will return to the Flow Rate display.
Pressing both UP and DOWN simultaneously when the Total Water is displayed resets the

Total Water accumulator to Zero.
Pressing both UP and DOWN simultaneously when the Total Product is displayed resets the

Total Product accumulator to Zero.
Pressing both UP and DOWN simultaneously when the Flow Rate is displayed enters the

MANUAL mode of operation. See Manual Mode operation below.
Pressing both UP and DOWN simultaneously while in Mix % will go to the default %.

FOAM

Pressing the FOAM key will alternately start and stop the foam operation. When the control-

ler is running, the FOAM LED will be lit. The FOAM LED will blink when the motor control

output is active. The LED will be lit and not blink during the initial pump delay, or when the

system is on, but no water flow is detected.
If flow is detected, and one or both of the sensor inputs reads full scale, an open sensor error

will be flagged. The error SEn1 or error SEn2 will be displayed when the FOAM button is

pressed to indicated that the system is non

functional. In this case, the Manual Mode will be

functional and must be used.

MANUAL MODE

If the display is showing the flow rate and the two ARROW keys are pressed simultaneously,

the % MIX LED will be lit and the display will show a default value of 2.0. Use the UP and

DOWN arrow keys to increase or decrease this value in steps of 0.5.

NOTE: Pump output is based on a theoretical ratio of foam to water at 50 GPM.

Pressing both ARROW keys again exits the MANUAL mode and stops the pump.

NOTE: Motor/Pump Assembly will operate in manual mode whether or not there is a

water flow. If the INJECT/BYPASS valve is in the INJECT position, foam concentrate

will be injected into the system, which will waste concentrate.

AUTO RUN

The system is equipped with an AUTO RUN feature. If the voltage (+12 or 24 VDC) is ap-

plied to position 1 on the terminal strip, it will have the same effect as pressing the Red

FOAM button. This will start the Foam system. The system will not inject foam until water is

flowing.

Summary of Contents for Advantus Foam Manager

Page 1: ...rvice and Maintenance 6 Maintenance Schedule 6 Location of Maintenance Items 6 Advantus Foam Pump 6 Oil Fill and Drain 6 In line Foam Concentrate Strainer 6 Calibration 7 Advantus Foam Pump 7 Troubleshooting Guide 8 Foam Manager with Advantus Waterous Company 125 Hardman Avenue South South St Paul Minnesota 55075 USA 651 450 5000 Instructions subject to change without notice Visit us at www watero...

Page 2: ... with pump intake or pump discharge connec tions relieve pressure by opening drains or bleeder valves Bleeder valves should also be used while filling a hose connected to an intake with water WARNING Scalding Water Hazard May result in serious burns When operating the pump be sure to open at least one discharge valve slightly to prevent the pump from overheating If the pump runs for a few minutes ...

Page 3: ...si 10 bar for the Advantus 6 with operating pressures up to 450 psi 32 bar The system draws a maximum electrical load of 40 amps 12 VDC or 21 amps 24 VDC Ad vantus 3 or 80 amps 12 VDC or 40 amps 24 VDC Advantus 6 A pump motor electronic driver located inside the controller housing receives signals from the microcontroller and powers the electric motor in a variable speed duty cycle to ensure that ...

Page 4: ...it can be operated in water only and or foam modes It is pos sible to pump water from one discharge and foam solution from another discharge Water Only Operations All unit operations begin with pumping water See the fol lowing instruction for details on how to operate and pump water from your Waterous fire pump F 1031 Section 2114 Operation and Maintenance Instructions for Waterous CMU Series Cent...

Page 5: ...ing both UP and DOWN simultaneously when the Total Product is displayed resets the Total Product accumulator to Zero Pressing both UP and DOWN simultaneously when the Flow Rate is displayed enters the MANUAL mode of operation See Manual Mode operation below Pressing both UP and DOWN simultaneously while in Mix will go to the default FOAM Pressing the FOAM key will alternately start and stop the fo...

Page 6: ...Port Capacity Required for Oil Change Use Oil Daily or After Each Use Annually Advantus 3 3 4 inch 19 mm 90 quarts Total capacity is 1 0 quart Synthetic 10W 30 Mobil 1 recommended Monthly Depending on the corrosiveness of the foam concentrate to be used flushing of the foam injection circuit may be necessary Most Class A foam concen trates are less corrosive and may not require flushing Advantus 6...

Page 7: ...the UP and DOWN arrow buttons to select one of the following measurement units GAL will select U S Gallons IPL will select Imperial Gallons LTR will select Metric Liters 3 Pushing the SELECT button will save the dis played selection This will allow for calibration of the water flow in the units of measurement selec ted D F3 Flow Rate Calibration 1 Press the SELECT button at the F3 prompt The curre...

Page 8: ...dition applies to tanks utilizing a common wall s between the foam tank and the water tank If a leak is confirmed repair the foam tank and flush the water tank and pump until foam is cleared Foam proportioning manifold check valve mal function If the above conditions have been corrected the final cause for foam in the water tank may be the result of a malfunctioning foam manifold check valve To tr...