Foam Operation

After the pump is operating, turn on the foam pump to in-

ject foam concentrate into the water stream.

Refer to Advantus Foam Pump Operation Instructions on

Page 5.

Foam System Flush

1. Turn off Foam Pump.

2. Flow clear water through discharges that were used

until clear water is flowing from the nozzle.

Service and Maintenance

Maintenance Schedule

Table 2. Maintenance Schedule 

 Foam Pump (See Figure 3)

Check Oil

Level and

for Oil

Leaks

Foam Pump Oil

Check and

Clean Foam

Concentrate

In

line

Strainer

Flushing System

Change

Foam

Pump

Model

Level from

Top of Oil

Fill Port

Capacity

Required for Oil

Change

Use Oil

Daily or

After Each

Use

Annually

Advantus 3

3/4 inch

(19 mm)

.90 quarts

(Total capacity is

1.0 quart)

Synthetic

10W

30

(Mobil 1

recommended)

Monthly

Depending on the corrosiveness of the

foam concentrate to be used, flushing of

the foam injection circuit may be

necessary. Most Class A foam concen-

trates are less corrosive and may not

require flushing.

Advantus 6

1 inch

(25 mm)

1.0 quarts

(Total capacity is

1.1 quarts)

Location of Maintenance Items

The following figures show the location of the Advantus Foam Pump oil fill and drain.

Figure 3.

 

Advantus

t

 Foam Pump Oil Fill and Drain, In

line Foam Concentrate Strainer

Advantus 3 Systems

Advantus 6 Systems

Oil Fill

Oil Drain

In

line Foam Concentrate Strainer

In

line Foam Concentrate Strainer

To Foam Tank

To Foam Tank

IL2959

Summary of Contents for Advantus Foam Manager

Page 1: ...rvice and Maintenance 6 Maintenance Schedule 6 Location of Maintenance Items 6 Advantus Foam Pump 6 Oil Fill and Drain 6 In line Foam Concentrate Strainer 6 Calibration 7 Advantus Foam Pump 7 Troubleshooting Guide 8 Foam Manager with Advantus Waterous Company 125 Hardman Avenue South South St Paul Minnesota 55075 USA 651 450 5000 Instructions subject to change without notice Visit us at www watero...

Page 2: ... with pump intake or pump discharge connec tions relieve pressure by opening drains or bleeder valves Bleeder valves should also be used while filling a hose connected to an intake with water WARNING Scalding Water Hazard May result in serious burns When operating the pump be sure to open at least one discharge valve slightly to prevent the pump from overheating If the pump runs for a few minutes ...

Page 3: ...si 10 bar for the Advantus 6 with operating pressures up to 450 psi 32 bar The system draws a maximum electrical load of 40 amps 12 VDC or 21 amps 24 VDC Ad vantus 3 or 80 amps 12 VDC or 40 amps 24 VDC Advantus 6 A pump motor electronic driver located inside the controller housing receives signals from the microcontroller and powers the electric motor in a variable speed duty cycle to ensure that ...

Page 4: ...it can be operated in water only and or foam modes It is pos sible to pump water from one discharge and foam solution from another discharge Water Only Operations All unit operations begin with pumping water See the fol lowing instruction for details on how to operate and pump water from your Waterous fire pump F 1031 Section 2114 Operation and Maintenance Instructions for Waterous CMU Series Cent...

Page 5: ...ing both UP and DOWN simultaneously when the Total Product is displayed resets the Total Product accumulator to Zero Pressing both UP and DOWN simultaneously when the Flow Rate is displayed enters the MANUAL mode of operation See Manual Mode operation below Pressing both UP and DOWN simultaneously while in Mix will go to the default FOAM Pressing the FOAM key will alternately start and stop the fo...

Page 6: ...Port Capacity Required for Oil Change Use Oil Daily or After Each Use Annually Advantus 3 3 4 inch 19 mm 90 quarts Total capacity is 1 0 quart Synthetic 10W 30 Mobil 1 recommended Monthly Depending on the corrosiveness of the foam concentrate to be used flushing of the foam injection circuit may be necessary Most Class A foam concen trates are less corrosive and may not require flushing Advantus 6...

Page 7: ...the UP and DOWN arrow buttons to select one of the following measurement units GAL will select U S Gallons IPL will select Imperial Gallons LTR will select Metric Liters 3 Pushing the SELECT button will save the dis played selection This will allow for calibration of the water flow in the units of measurement selec ted D F3 Flow Rate Calibration 1 Press the SELECT button at the F3 prompt The curre...

Page 8: ...dition applies to tanks utilizing a common wall s between the foam tank and the water tank If a leak is confirmed repair the foam tank and flush the water tank and pump until foam is cleared Foam proportioning manifold check valve mal function If the above conditions have been corrected the final cause for foam in the water tank may be the result of a malfunctioning foam manifold check valve To tr...

Reviews: