background image

F

1031, Section 2407

Page 3 of 8

Introduction

System Overview

NOTE: Read and understand the operating instruc-

tions for the Foam Manager System prior to operating.

(Refer to Figure 1 for system components.)

The Foam Manager

t

 System consists of an Advantus

t

Foam Management System mounted on a Waterous CM

or CS fire pump.

Advantus

t

 3/6 Foam Management System

The ADVANTUS

t

 foam system uses advanced conductiv-

ity

based technology to monitor both supply water and

foam solution in order to deliver optimal foam at every call.

Regardless of the foam concentrate or the quality of the

water being pumped, the ADVANTUS automatically adjusts

for both, providing you with the most accurate fire suppres-

sion capabilities in the industry.

Foam Pump

The 12 or 24

volt electric motor driven, Hydra

Cell positive

displacement foam concentrate pump is constructed of

brass and stainless steel components which may come in

contact with foam concentrate, making the pump resistant

to chemical and corrosive attack. The pump is capable of

handling suspended abrasives without sustaining any dam-

age and can run dry for extended periods without sustain-

ing damage.

The foam pump for the Advantus 3 is rated at 3 GPM (11.3

l/min) at 150 psi (10 bar) and 6 GPM (22.6 l/min at 150 psi

(10 bar) for the Advantus 6, with operating pressures up to

450 psi (32 bar). The system draws a maximum electrical

load of 40 amps @ 12 VDC or 21 amps @ 24 VDC (Ad-

vantus 3) or 80 amps @ 12 VDC or 40 amps @ 24 VDC

(Advantus 6).
A pump motor electronic driver, located inside the controller

housing receives signals from the microcontroller and

powers the electric motor in a variable speed duty cycle to

ensure that the correct amount of foam concentrate as set

by the pump operator is injected into the water stream.

Process Manifold

The foam system process manifold, constructed of stain-

less steel with Victaulic

®

 groove connections provided at

each end of the manifold for connection to the apparatus

plumbing. The process manifold includes an incoming

water conductivity probe, paddlewheel flowmeter, foam

injection check valve, Akron Brass

®

 waterway check valve

and foam solution conductivity probe. An Akron full

flow

brass body check valve in the foam process manifold

waterway prevents foam contamination of fire pump and

water supply. A brass and stainless steel check valve

provided in the foam concentrate line at the foam injection

point to prevents water backflow into the foam supply res-

ervoir(s). Stainless steel conductivity probes include gap

spacers and a reverse charge feature to prevent build

up

of deposits on the probe surfaces.
The  system also incorporate a sensor to measure water

temperature to ensure the proper amount of concentrate is

injected.

Summary of Contents for Advantus Foam Manager

Page 1: ...rvice and Maintenance 6 Maintenance Schedule 6 Location of Maintenance Items 6 Advantus Foam Pump 6 Oil Fill and Drain 6 In line Foam Concentrate Strainer 6 Calibration 7 Advantus Foam Pump 7 Troubleshooting Guide 8 Foam Manager with Advantus Waterous Company 125 Hardman Avenue South South St Paul Minnesota 55075 USA 651 450 5000 Instructions subject to change without notice Visit us at www watero...

Page 2: ... with pump intake or pump discharge connec tions relieve pressure by opening drains or bleeder valves Bleeder valves should also be used while filling a hose connected to an intake with water WARNING Scalding Water Hazard May result in serious burns When operating the pump be sure to open at least one discharge valve slightly to prevent the pump from overheating If the pump runs for a few minutes ...

Page 3: ...si 10 bar for the Advantus 6 with operating pressures up to 450 psi 32 bar The system draws a maximum electrical load of 40 amps 12 VDC or 21 amps 24 VDC Ad vantus 3 or 80 amps 12 VDC or 40 amps 24 VDC Advantus 6 A pump motor electronic driver located inside the controller housing receives signals from the microcontroller and powers the electric motor in a variable speed duty cycle to ensure that ...

Page 4: ...it can be operated in water only and or foam modes It is pos sible to pump water from one discharge and foam solution from another discharge Water Only Operations All unit operations begin with pumping water See the fol lowing instruction for details on how to operate and pump water from your Waterous fire pump F 1031 Section 2114 Operation and Maintenance Instructions for Waterous CMU Series Cent...

Page 5: ...ing both UP and DOWN simultaneously when the Total Product is displayed resets the Total Product accumulator to Zero Pressing both UP and DOWN simultaneously when the Flow Rate is displayed enters the MANUAL mode of operation See Manual Mode operation below Pressing both UP and DOWN simultaneously while in Mix will go to the default FOAM Pressing the FOAM key will alternately start and stop the fo...

Page 6: ...Port Capacity Required for Oil Change Use Oil Daily or After Each Use Annually Advantus 3 3 4 inch 19 mm 90 quarts Total capacity is 1 0 quart Synthetic 10W 30 Mobil 1 recommended Monthly Depending on the corrosiveness of the foam concentrate to be used flushing of the foam injection circuit may be necessary Most Class A foam concen trates are less corrosive and may not require flushing Advantus 6...

Page 7: ...the UP and DOWN arrow buttons to select one of the following measurement units GAL will select U S Gallons IPL will select Imperial Gallons LTR will select Metric Liters 3 Pushing the SELECT button will save the dis played selection This will allow for calibration of the water flow in the units of measurement selec ted D F3 Flow Rate Calibration 1 Press the SELECT button at the F3 prompt The curre...

Page 8: ...dition applies to tanks utilizing a common wall s between the foam tank and the water tank If a leak is confirmed repair the foam tank and flush the water tank and pump until foam is cleared Foam proportioning manifold check valve mal function If the above conditions have been corrected the final cause for foam in the water tank may be the result of a malfunctioning foam manifold check valve To tr...

Reviews: