TROUBLESHOOTING
Compressor is Not Running
Possible Reason
Solution
Green Heater / Compressor
Switch button on unit is in the
off position
Turn Green Heater/Compressor r switch on.
I = ON
Compressor Starting Circuit
Turn Green Heater/Compressor switch off.
O =
OFF.
Remove the compressor cap on side of the
compressor;
Disconnect the black and red terminal connectors;
Inspect the starter and overload relay for any defects.
Replace components(s) as needed.
Turn Green Heater/Compressor switch on
I = O and
retest
compressor operation.
WL400
Operating, Installation, and Service Manual Page 69 - Revision: 5-29-2015