background image

12

SYNERGY3D INSTALLATION MANUAL

The unit uses an external temperature sensor such as the 
lower thermostat in a water heater storage tank to control the 
tank temperature. The thermostat should be wired to the unit 
P5 connector wires, P5-11 and P5-4 tan wires.  When the tank 
temperature drops below the thermostat setting the contacts in the 
thermostat will close and initiate a signal to the unit to heat water.

A storage tank must be used to store the heated water supplied by 
the unit. It is not recommended to send heated water from the unit 
directly to the hydronic zones since the unit also has the ability to 
condition the space with forced air. There must be adequate storage 
capacity in the storage tank to accommodate the hydronic load 
while the unit is operating in forced air mode.  The hydronic storage 
tank should be sized to provide 2 gallons of storage capacity for 
every one thousand Btuh’s of nominal heat pump capacity.

Adequate rate of flow (GPM) is very important to system performance 
and long term reliability. Follow the guidelines for recommended flow 
and pipe sizing in the unit recommendations table.

Be sure to burp the pump. Open the screw 2 turns only in the 
end of the pump motor (if Grundfos

®

 pumps are used) to allow 

trapped air to be discharged and to ensure the motor housing has 
been flooded.

The red “courtesy” wires exit out of the top of the tank. The wires 
must be connected to the tank thermostat and to P5 tan connector 
wires, P5-11 and P5-4 on the main logic board.

Hydronic Section cont.

WaterFurnace Geothermal Storage Tank Thermostat

Synergy3D must be wired to the thermostat screw 

terminals. The yellow thermistor wires will not operate 

with the Synergy3D as they are used with the NSW Series 

water-to-water.

Thermostat

Summary of Contents for Synergy3D

Page 1: ...tions Hot Water Generator Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance Synergy3D Installation Manual Geothermal Heat Pump with Water Heating for Radiant Floor Appli...

Page 2: ......

Page 3: ...iary Heat 15 Electrical Data 16 Blower Performance Data 17 Dimensional Data 18 Physical Data 20 Microprocessor Control 21 Operation Logic 25 Wiring Schematics 26 Unit Startup 30 Operating Parameters 3...

Page 4: ...IntelliStart Control Option S Microprocessor Filter Option 0 2 inch MERV11 Filter 1 AlpinePure 411 Return Air Configuration L Left R Right Discharge Air Configuration T Top Vertical R Rear Vertical Wa...

Page 5: ...checked against the bill of lading to be sure all crates and cartons have been received Examine units for shipping damage removing the units from the packaging if necessary Units in question should a...

Page 6: ...ithout the need for thread sealing tape or compound Check to ensure that the rubber seal is in the swivel connector prior to attempting any connection The rubber seals are shipped attached to the wate...

Page 7: ...n 1 ppm above this level deposition will occur Less than 1 ppm above this level deposition will occur Erosion Suspended Solids Less than 10 ppm and filtered for max of 600 micron size Less than 10 ppm...

Page 8: ...k Polyethylene w Armaflex TO LOOP Auxiliary Heater Knockout Low Voltage to Thermostat Unit Power Unit Supply Auxiliary Heat Supply For complete information refer to GeoLink Flow Center Installation Ma...

Page 9: ...For HX Flushing Strainer Low Voltage to Thermostat and Valve Unit Power Shut Off Valves to isolate solenoid valve while acid flushing Shut Off Valves Water Out Water In Solenoid Valve Flow Control Val...

Page 10: ...aters connected in a series Electric water heaters are recommended Make sure all local electrical and plumbing codes are met for installing a hot water generator The Synergy3D is not supplied with an...

Page 11: ...h must be cleaned after the initial filling If there is a restriction in the screen the system could go to 0 psi 0 kPa potentially causing pumps s failure A valve should be installed on each side of t...

Page 12: ...forced air mode The hydronic storage tank should be sized to provide 2 gallons of storage capacity for every one thousand Btuh s of nominal heat pump capacity Adequate rate of flow GPM is very importa...

Page 13: ...rnal Loop Pump Power Connection If the unit is to be used with an external loop pump FC1 or FC2 flow center the pump s will be connected to the terminals on PB1 in the unit electrical box as shown The...

Page 14: ...ring the same wiring See instructions enclosed in the thermostat for detailed installation and operation information Other Thermostats The Synergy3D unit is compatible with virtually any 24VAC thermos...

Page 15: ...00 1500 5 6 09 Model Supply Circuit Heater Amps Min Circuit Amp Max Fuse USA Max Fuse CAN Max CKT BRK 208V 240V 208V 240V 208V 240V 208V 240V 208V 240V EAL H 10A Single 34 7 40 53 3 60 60 60 60 60 60...

Page 16: ...32 5 45 049 208 230 60 1 187 254 33 0 21 1 104 0 37 0 1 07 5 4 4 0 31 6 36 8 50 049 208 230 60 1 187 254 33 0 21 1 104 0 37 0 1 07 5 4 7 0 34 6 39 9 60 064 208 230 60 1 187 254 42 3 27 1 152 9 54 0 1...

Page 17: ...ow Speed Blower 800 CFM Medium Speed Blower 1350 CFM High Speed Blower 1550 CFM AE Model Max ESP Air Flow Dip Switch Settings 1 2 3 4 5 6 7 8 9 10 11 12 038 0 50 650 750 850 1000 1100 1200 1300 1400 1...

Page 18: ...2 Female 14 4 36 6 12 1 30 7 9 6 24 4 Condensate is 3 4 in PVC female glue socket and is switchable from side to front Unit shipped with deluxe 2 in field adjustable to 1 in duct collar filter rack e...

Page 19: ...wivel 1 Swivel 1 2 Female 14 4 36 6 12 1 30 7 9 6 24 4 064 in cm 25 6 65 0 31 6 80 3 58 4 148 3 7 3 18 5 18 9 48 0 2 3 5 8 15 9 40 4 15 9 40 4 18 9 48 0 10 6 26 9 1 Swivel 1 Swivel 1 2 Female 14 4 36...

Page 20: ...nections Size Swivel in mm 1 25 4 1 25 4 1 25 4 1 25 4 HWG Connection Size Female Sweat I D in mm 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 Coax Piping Water Volume gal l 1 3 4 9 1 6 6 1 1 6 6 1 1 6 6 1 Ver...

Page 21: ...tion Microprocessor Control Testing The control allows service personnel to shorten most timing delays for faster diagnostics Refer to Dip Switch description Fault Retry All faults except for low RPM...

Page 22: ...t 24VAC signal is removed the control will turn off the CR3 relay output if spring damper operation is selected or activate the CR4 output if POPC damper operation is selected This will close field in...

Page 23: ...R R R R R G Y R ComforTalk and FaultFlash Thermostats When the heat pump microprocessor control is configured for ComforTalk or FaultFlash SW2 8 off thermostats the thermostats will flash or display a...

Page 24: ...loop pump on the LED display Outputs Normal SW2 8 Thermostat Selection Configures the control for a pulsed lockout signal ComforTalk and FaultFlash thermostats or continuous lockout signal standard th...

Page 25: ...n On Off Loop Pump On On On Off On On On Load Pump Off Off Off Off Off Off On Aux Heater Off Off Staged Staged Off Off Off Acc Relay On On On Off On On Off Diverting Valve Off Off Off Off Off Off On E...

Page 26: ...6 7 8 1 2 3 P4 Black Black Orange Orange 1 2 3 C P2 Down C 1 2 3 4 5 6 7 Shut SL1 In Not SL1 Out Used Status LED PCB SW4 R R R R R G Y R 1 2 3 Pulse L Constant L See Note 6 Not Used FAH Hydronic Loop...

Page 27: ...limit switch Relay Contacts N O N C G T 1 3 2 P L1 PSC Fan Speed Relay PSC Fan Power Relay ER1 to ER4 Aux heat stage relays HWL Hot water limit sensor CS Compressor Solenoid Legend PR Pump Relay Break...

Page 28: ...11 2 10 8 1 12 5 14 13 6 7 P6 6 5 4 8 7 12 1 2 9 10 3 13 14 16 11 15 Blk 20 Acc Com Acc NC Acc NO P3 SV Blk 23 White 22 NOTE 2 ECM Fan Motor Grn 15 10 16 3 8 On Off PWM RPM C2 RPM grnd P12 P11 2 3 4...

Page 29: ...R1 to ER4 Aux heat stage relays HWL Hot water limit sensor CS Compressor Solenoid Legend PR Pump Relay Breaker 2 3 P9 5 4 1 L2 L1 L2 L1 G G Circuit 1 Circuit 2 NOTE 2 208 230 60 1 208 230 60 1 Green C...

Page 30: ...system to desired normal operating temperature to maintain desired comfort level 9 Instruct the owner operator in the proper operation of the hydronic temperature control and system maintenance Forced...

Page 31: ...ater Temp Rise F Air Temp Drop F DB Suction Pressure PSIG Discharge Pressure PSIG Super heat F Sub cooling F Water Temp Rise F Air Temp Drop F DB 20 1 5 Operation Not Recommended Operation Not Recomme...

Page 32: ...6 3 4 3 2 2 9 15 5 7 5 3 5 0 4 7 4 3 049 part load 5 1 1 1 1 1 0 0 9 0 9 8 2 0 1 8 1 7 1 6 1 5 11 3 4 3 1 2 9 2 8 2 5 14 5 0 4 7 4 4 4 1 3 8 064 full load 8 2 0 1 8 1 7 1 6 1 5 12 3 6 3 3 3 2 3 0 2 6...

Page 33: ...72 1 99 064 ZPS51K5E PFV 0 36 0 42 1 51 1 74 072 ZPS60K5E PFV 0 31 0 36 1 72 1 98 9 24 2013 Thermistor Temperature F Microprocessor Resistance Ohms 5 75757 70117 14 57392 53234 23 43865 40771 32 3380...

Page 34: ...0 42 2 40 0 46 9 44 9 43 2 40 8 Full Load 6 0 31 3 39 4 43 7 55 5 53 3 50 3 9 0 23 2 32 5 41 5 46 6 48 7 55 6 53 8 51 3 49 6 12 0 23 6 33 4 42 8 48 3 48 8 55 7 54 1 51 4 49 8 064 Part Load 6 0 29 8 39...

Page 35: ...ing Heating CFM Per Ton of Clg of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext 240 60 0 922 0 786 0 910 0 920 0 943 1 150 0 893 275 69 0 944 0 827 0 924 0 940 0 958 1 105 0 9...

Page 36: ...ure drop in feet of head GPM Gallons per minute WPD water pressure drop psi and feet of water HC air heating capacity MBtu h HE total heat of extraction MBtu h HR total heat of rejection MBtu h kW tot...

Page 37: ...nown to be correct gauges should then be installed and superheat and subcooling numbers calculated If superheat and subcooling are outside recommended ranges an adjustment to the refrigerant charge ma...

Page 38: ...___ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o x 3 413 p _____ btu hr 7 EFFICIENCY Cooling EER p...

Page 39: ..._SAT F ______ F ______PSI ______SAT F ______ F F F NOTE Do not attach refrigerant gauges unless a problem is suspected FD TXV CV Suction Discharge Compressor RV Air Coil Source Coax Load Coax DV open...

Page 40: ...___SAT F ______ F ______ F Liquid Line Unit Amp Draw ____________ Line Voltage _________ Loop ______ Open ______ Closed Subcooling _______ Superheat _______ NOTE Do not attach refrigerant gauges unles...

Page 41: ...erated without a filter Obtaining Parts When ordering service or replacement parts refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit If replac...

Page 42: ...8 33P619 09 DanfossTXV model TR6 3 Ton 3 8 TR6 4 Ton 1 2 TR6 5 Ton 1 2 TR6 6 Ton 1 2 Reversing Valve 33P503 05 33P526 05 Diverting Valve 33P503 05 33P526 05 Filter Drier 36P500B01 36P500B02 Refrigeran...

Page 43: ...d Nomenclature Hot Water Generation Option updated Open Loop Solenoid Valve Connection Option Wiring Diagrams 30 Sept 2014 MA All Updated to new Revision Reformatted Layout 27 Dec 2013 DS All Updated...

Page 44: ...n Way Fort Wayne IN 46809 9794 WaterFurnace has a policy of continual product research and development and reserves the right to change design and speci cations without notice IM1300YS 07 15 Product S...

Reviews: