background image

11

SYNERGY3D INSTALLATION MANUAL

General guidelines are shown below for component 

selection and design/installation criteria for the piping 

system. Local codes supersede any recommendations in 

this manual.

Shut off/flow regulation valves:

 Use full port ball valves or 

gate valves for component isolation. If valves are going to 

be used frequently, ball valves are recommended. Globe 

valves are designed for flow regulation. Always install globe 

valves in the correct direction (fluid should enter through 

the lower body chamber).

Check valves:

 Swing check valves must be installed in the 

horizontal position with the bonnet of the valve upright.  

Spring check valves can be mounted in any position. A flow 

check valve is required to prevent thermo-siphoning (or 

gravity flow) when the circulator pump is off or when there 

are two circulators on the same system.

Storage (Buffer) tank:

 A buffer tank is required for all 

hydronic heating systems using Synergy3D heat pumps.  

The tank should be sized to provide 2 gallons of storage 

capacity for every one thousand btuh’s of nominal heat 

pump capacity.

Pressure relief valve:

 Most codes require the use of a 

pressure relief valve if a closed loop heat source can be 

isolated by valves. Even if local code does not require 

this device, WaterFurnace recommends its installation. If 

the pressure relief valve in the buffer tank is not already 

rated at 30 psi (207 kPa) maximum pressure, one must be 

installed. The pressure relief valve should be tested at start 

up for operation. This valve can also be used during initial 

filling of the system to purge air.  Note that the waste pipe 

must be at least the same diameter as the valve outlet 

(never reduce), and valves may not be added to this pipe.  

The bottom of the pipe must terminate at least 6” (15 cm) 

above the floor.  If the piping is connected to a drain, there 

must be an air gap.

Backflow prevention check valves:

 Most codes require 

backflow prevention check valves. Note that a single 

check valve is not equal to a backflow prevention check 

valve. Even if local code does not require this device, 

WaterFurnace recommends its installation. This is 

particularly important if the system will use antifreeze.  

Pressure reducing valves or feed water valves: 

This valve 

lowers the pressure from the make-up water line to the 

system. Most are adjustable and directional. A “fast fill” 

valve is required for initial filling of the system. Some have 

screens, which must be cleaned after the initial filling. If 

there is a restriction in the screen, the system could go to 

0 psi (0 kPa), potentially causing pumps(s) failure. A valve 

should be installed on each side of the pressure reducing 

Hydronic Section

valve for servicing. Both valves should have tags reading 

“Do not shut this valve under normal operation – service 

valve only”.

Expansion tanks: 

Expansion tanks are required on hydronic 

systems to help absorb the pressure swings as the 

temperature in the system fluctuates.

Elbows/tees:

 Long radius elbows or two 45° elbows 

will lower pressure drop.  Standard tees have a greater 

restriction on the “T” portion than tees designed with 

angled outlet ports.

Antifreeze:

 Antifreeze is required if any of the piping 

system is located in areas subject to freezing.

Dielectric unions:

 Dielectric unions are recommended 

whenever connecting two dissimilar metals to one and 

other to prevent electro-galvanic corrosion.

When using the various types of hydronic heat distribution 

systems, the temperature limits of the geothermal system 

must be a major consideration. In new construction, 

the distribution system can easily be designed with the 

temperature limits in mind. In retrofits, care must be 

taken to address the operating temperature limits of the 

existing distribution system. The maximum storage tank 

temperature for the Synergy3D is 130°F (54.4°C). Typical 

in floor radiant systems require much lower temperatures, 

typically 100°-115°F, which is ideal for the Synergy3D.  

The Synergy3D uses an external temperature sensor such 

as the lower thermostat in a water heater storage tank to 

control the tank temperature. The thermostat should be 

wired to the Synergy3D P5 connector wires, P5-11 and P5-4 

tan wires.  When the tank temperature drops below the 

thermostat setting the contacts in the thermostat will close 

and initiate a signal to the Synergy3D to heat water.

A storage tank must be used to store the heated water 

supplied by the Synergy3D. It is not recommended to send 

heated water from the Synergy3D directly to the hydronic 

zones since the Synergy3D also has the ability to condition 

the space with forced air. There must be adequate storage 

capacity in the storage tank to accommodate the hydronic 

load while the Synergy3D is operating in forced air mode.  

The hydronic storage tank should be sized to provide 2 

gallons of storage capacity for every one thousand Btuh’s 

of nominal heat pump capacity.

Adequate rate of flow (GPM) is very important to system 

performance and long term reliability. Follow the guidelines 

for recommended flow and pipe sizing in the Synergy3D 

Recommendations table.

Summary of Contents for Synergy3D

Page 1: ...tions Hot Water Generator Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance Synergy3D Installation Manual Geothermal Heat Pump with Water Heating for Radiant Floor Appli...

Page 2: ......

Page 3: ...iary Heat 15 Electrical Data 16 Blower Performance Data 17 Dimensional Data 18 Physical Data 20 Microprocessor Control 21 Operation Logic 25 Wiring Schematics 26 Unit Startup 30 Operating Parameters 3...

Page 4: ...IntelliStart Control Option S Microprocessor Filter Option 0 2 inch MERV11 Filter 1 AlpinePure 411 Return Air Configuration L Left R Right Discharge Air Configuration T Top Vertical R Rear Vertical Wa...

Page 5: ...checked against the bill of lading to be sure all crates and cartons have been received Examine units for shipping damage removing the units from the packaging if necessary Units in question should a...

Page 6: ...ithout the need for thread sealing tape or compound Check to ensure that the rubber seal is in the swivel connector prior to attempting any connection The rubber seals are shipped attached to the wate...

Page 7: ...n 1 ppm above this level deposition will occur Less than 1 ppm above this level deposition will occur Erosion Suspended Solids Less than 10 ppm and filtered for max of 600 micron size Less than 10 ppm...

Page 8: ...k Polyethylene w Armaflex TO LOOP Auxiliary Heater Knockout Low Voltage to Thermostat Unit Power Unit Supply Auxiliary Heat Supply For complete information refer to GeoLink Flow Center Installation Ma...

Page 9: ...For HX Flushing Strainer Low Voltage to Thermostat and Valve Unit Power Shut Off Valves to isolate solenoid valve while acid flushing Shut Off Valves Water Out Water In Solenoid Valve Flow Control Val...

Page 10: ...aters connected in a series Electric water heaters are recommended Make sure all local electrical and plumbing codes are met for installing a hot water generator The Synergy3D is not supplied with an...

Page 11: ...h must be cleaned after the initial filling If there is a restriction in the screen the system could go to 0 psi 0 kPa potentially causing pumps s failure A valve should be installed on each side of t...

Page 12: ...forced air mode The hydronic storage tank should be sized to provide 2 gallons of storage capacity for every one thousand Btuh s of nominal heat pump capacity Adequate rate of flow GPM is very importa...

Page 13: ...rnal Loop Pump Power Connection If the unit is to be used with an external loop pump FC1 or FC2 flow center the pump s will be connected to the terminals on PB1 in the unit electrical box as shown The...

Page 14: ...ring the same wiring See instructions enclosed in the thermostat for detailed installation and operation information Other Thermostats The Synergy3D unit is compatible with virtually any 24VAC thermos...

Page 15: ...00 1500 5 6 09 Model Supply Circuit Heater Amps Min Circuit Amp Max Fuse USA Max Fuse CAN Max CKT BRK 208V 240V 208V 240V 208V 240V 208V 240V 208V 240V EAL H 10A Single 34 7 40 53 3 60 60 60 60 60 60...

Page 16: ...32 5 45 049 208 230 60 1 187 254 33 0 21 1 104 0 37 0 1 07 5 4 4 0 31 6 36 8 50 049 208 230 60 1 187 254 33 0 21 1 104 0 37 0 1 07 5 4 7 0 34 6 39 9 60 064 208 230 60 1 187 254 42 3 27 1 152 9 54 0 1...

Page 17: ...ow Speed Blower 800 CFM Medium Speed Blower 1350 CFM High Speed Blower 1550 CFM AE Model Max ESP Air Flow Dip Switch Settings 1 2 3 4 5 6 7 8 9 10 11 12 038 0 50 650 750 850 1000 1100 1200 1300 1400 1...

Page 18: ...2 Female 14 4 36 6 12 1 30 7 9 6 24 4 Condensate is 3 4 in PVC female glue socket and is switchable from side to front Unit shipped with deluxe 2 in field adjustable to 1 in duct collar filter rack e...

Page 19: ...wivel 1 Swivel 1 2 Female 14 4 36 6 12 1 30 7 9 6 24 4 064 in cm 25 6 65 0 31 6 80 3 58 4 148 3 7 3 18 5 18 9 48 0 2 3 5 8 15 9 40 4 15 9 40 4 18 9 48 0 10 6 26 9 1 Swivel 1 Swivel 1 2 Female 14 4 36...

Page 20: ...nections Size Swivel in mm 1 25 4 1 25 4 1 25 4 1 25 4 HWG Connection Size Female Sweat I D in mm 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 Coax Piping Water Volume gal l 1 3 4 9 1 6 6 1 1 6 6 1 1 6 6 1 Ver...

Page 21: ...tion Microprocessor Control Testing The control allows service personnel to shorten most timing delays for faster diagnostics Refer to Dip Switch description Fault Retry All faults except for low RPM...

Page 22: ...t 24VAC signal is removed the control will turn off the CR3 relay output if spring damper operation is selected or activate the CR4 output if POPC damper operation is selected This will close field in...

Page 23: ...R R R R R G Y R ComforTalk and FaultFlash Thermostats When the heat pump microprocessor control is configured for ComforTalk or FaultFlash SW2 8 off thermostats the thermostats will flash or display a...

Page 24: ...loop pump on the LED display Outputs Normal SW2 8 Thermostat Selection Configures the control for a pulsed lockout signal ComforTalk and FaultFlash thermostats or continuous lockout signal standard th...

Page 25: ...n On Off Loop Pump On On On Off On On On Load Pump Off Off Off Off Off Off On Aux Heater Off Off Staged Staged Off Off Off Acc Relay On On On Off On On Off Diverting Valve Off Off Off Off Off Off On E...

Page 26: ...6 7 8 1 2 3 P4 Black Black Orange Orange 1 2 3 C P2 Down C 1 2 3 4 5 6 7 Shut SL1 In Not SL1 Out Used Status LED PCB SW4 R R R R R G Y R 1 2 3 Pulse L Constant L See Note 6 Not Used FAH Hydronic Loop...

Page 27: ...limit switch Relay Contacts N O N C G T 1 3 2 P L1 PSC Fan Speed Relay PSC Fan Power Relay ER1 to ER4 Aux heat stage relays HWL Hot water limit sensor CS Compressor Solenoid Legend PR Pump Relay Break...

Page 28: ...11 2 10 8 1 12 5 14 13 6 7 P6 6 5 4 8 7 12 1 2 9 10 3 13 14 16 11 15 Blk 20 Acc Com Acc NC Acc NO P3 SV Blk 23 White 22 NOTE 2 ECM Fan Motor Grn 15 10 16 3 8 On Off PWM RPM C2 RPM grnd P12 P11 2 3 4...

Page 29: ...R1 to ER4 Aux heat stage relays HWL Hot water limit sensor CS Compressor Solenoid Legend PR Pump Relay Breaker 2 3 P9 5 4 1 L2 L1 L2 L1 G G Circuit 1 Circuit 2 NOTE 2 208 230 60 1 208 230 60 1 Green C...

Page 30: ...system to desired normal operating temperature to maintain desired comfort level 9 Instruct the owner operator in the proper operation of the hydronic temperature control and system maintenance Forced...

Page 31: ...ater Temp Rise F Air Temp Drop F DB Suction Pressure PSIG Discharge Pressure PSIG Super heat F Sub cooling F Water Temp Rise F Air Temp Drop F DB 20 1 5 Operation Not Recommended Operation Not Recomme...

Page 32: ...6 3 4 3 2 2 9 15 5 7 5 3 5 0 4 7 4 3 049 part load 5 1 1 1 1 1 0 0 9 0 9 8 2 0 1 8 1 7 1 6 1 5 11 3 4 3 1 2 9 2 8 2 5 14 5 0 4 7 4 4 4 1 3 8 064 full load 8 2 0 1 8 1 7 1 6 1 5 12 3 6 3 3 3 2 3 0 2 6...

Page 33: ...72 1 99 064 ZPS51K5E PFV 0 36 0 42 1 51 1 74 072 ZPS60K5E PFV 0 31 0 36 1 72 1 98 9 24 2013 Thermistor Temperature F Microprocessor Resistance Ohms 5 75757 70117 14 57392 53234 23 43865 40771 32 3380...

Page 34: ...0 42 2 40 0 46 9 44 9 43 2 40 8 Full Load 6 0 31 3 39 4 43 7 55 5 53 3 50 3 9 0 23 2 32 5 41 5 46 6 48 7 55 6 53 8 51 3 49 6 12 0 23 6 33 4 42 8 48 3 48 8 55 7 54 1 51 4 49 8 064 Part Load 6 0 29 8 39...

Page 35: ...ing Heating CFM Per Ton of Clg of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext 240 60 0 922 0 786 0 910 0 920 0 943 1 150 0 893 275 69 0 944 0 827 0 924 0 940 0 958 1 105 0 9...

Page 36: ...ure drop in feet of head GPM Gallons per minute WPD water pressure drop psi and feet of water HC air heating capacity MBtu h HE total heat of extraction MBtu h HR total heat of rejection MBtu h kW tot...

Page 37: ...nown to be correct gauges should then be installed and superheat and subcooling numbers calculated If superheat and subcooling are outside recommended ranges an adjustment to the refrigerant charge ma...

Page 38: ...___ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o x 3 413 p _____ btu hr 7 EFFICIENCY Cooling EER p...

Page 39: ..._SAT F ______ F ______PSI ______SAT F ______ F F F NOTE Do not attach refrigerant gauges unless a problem is suspected FD TXV CV Suction Discharge Compressor RV Air Coil Source Coax Load Coax DV open...

Page 40: ...___SAT F ______ F ______ F Liquid Line Unit Amp Draw ____________ Line Voltage _________ Loop ______ Open ______ Closed Subcooling _______ Superheat _______ NOTE Do not attach refrigerant gauges unles...

Page 41: ...erated without a filter Obtaining Parts When ordering service or replacement parts refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit If replac...

Page 42: ...8 33P619 09 DanfossTXV model TR6 3 Ton 3 8 TR6 4 Ton 1 2 TR6 5 Ton 1 2 TR6 6 Ton 1 2 Reversing Valve 33P503 05 33P526 05 Diverting Valve 33P503 05 33P526 05 Filter Drier 36P500B01 36P500B02 Refrigeran...

Page 43: ...d Nomenclature Hot Water Generation Option updated Open Loop Solenoid Valve Connection Option Wiring Diagrams 30 Sept 2014 MA All Updated to new Revision Reformatted Layout 27 Dec 2013 DS All Updated...

Page 44: ...n Way Fort Wayne IN 46809 9794 WaterFurnace has a policy of continual product research and development and reserves the right to change design and speci cations without notice IM1300YS 07 15 Product S...

Reviews: