background image

6

Fig.3

All  register  plates,  restrictor  plates,  damper  etc.,
which could obstruct the flue at a future date should
be removed before connecting this appliance.

If  connecting  to  an  existing  chimney  with  a  flue
diameter of more that 8” it is recommend to line the
flue using a suitable stainless steel flue liner.

Where a masonry chimney is not available a propri-
etary  type  of  6”/150mm  -  twin  wall,  fully  insulated
pipe  may  be  used.    The  pipe  must  terminate  at  a
point not lower than the main ridge of adjacent out-
side obstructions.  With such installation, access to
the chimney must be provided for cleaning purpos-
es.  

A chimney / flue termination must be located to min-
imise wind effects, a basic guide is that the distance
from  the termination to the  roof  should  be at be at
least  2300mm  when  measured  horizontally  and  at
least  1000mm  when  measured  vertically,  (see
Fig.1).  In  circumstances  where  there  are  adjoining
buildings/  structures/ roof  openings  there  are  addi-
tional requirements, please refer to building regula-
tions part J.

Fig.1

2300

1

00

0

Appliance

Soot Door

The  stove  comes  partially  configured  for  top  outlet
and requires the flue spigot (supplied in the firebox)
to be fitted to the top outlet flue connection as shown
in Fig 3 using the nuts & bolts provided. 

To configure for back outlet flue connection, remove
the top plate and remove the back heat shield by lift-
ing  it  up  to  remove  it  from  its  four  fixing  points.
Remove the flue blanking plate from the back outlet
connection.  Remove  the  flue  spigot  from  the  top
connection and fit it to the back outlet connection. Fit
the flue blanking plate to the top outlet connection.
Remove the cut-out on the back heat shield and refit
the heat shield. Refit the hob and fit the hob blank-
ing plate (see Fig 4).

Fig.2

Debris Collection
space

Soot Door

Flue

Flue Liner

Sleeve

Flue Pipe

Possible
Positions 
for access

Appliance Flue
Outlet

Appliance 

FLUE EXIT (TOP & REAR)

The  stove  is  designed  to  allow  the  chimney  to  be
cleaned through the stove. If the chimney cannot be
cleaned through the stove it is necessary to provide
a soot box/ access door in the flue for cleaning. See
Fig.2 for recommended locations. Fit it to the stove
as shown in Fig.2.

Summary of Contents for STANLEY Solis F500 Edge

Page 1: ...ould be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the boiler stove in situations where ch...

Page 2: ...ation 9 14 Clearance To Combustibles 9 15 Floor Protection 9 16 Stove Dimensions 10 17 Commissioning and Handover 10 18 Operation 10 19 Air Controls 10 20 Recommended Fuels 11 21 Technical Data 11 22...

Page 3: ...nts or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part due to manufacturing defect that fails within the warranty period under the terms of the war...

Page 4: ...other appliance 8 Access should be provided to the chimney serving the appliance to allow for cleaning 9 It is a requirement by Building Regulations to have a carbon monoxide alarm fitted to any room...

Page 5: ...STICKING TO THE PAINT DURING THE CURING PROCESS 4 Inspect the flue ways of the stove weekly and ensure that there are no blockages Check flue ways before lighting especially after a shut down period...

Page 6: ...and Local Codes It should be noted that the requirements and these publications may be superseded during the life of this manual Please refer to the current standards BS EN 15287 1 2007 Design Instal...

Page 7: ...building regula tions part J Fig 1 2300 1000 Appliance Soot Door The stove comes partially configured for top outlet and requires the flue spigot supplied in the firebox to be fitted to the top outlet...

Page 8: ...ted output NOTE There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit smoke and fumes into the room All materials used in the manufacture of air v...

Page 9: ...e stove to be ducted from outside and is avail able to order for connection to the stove It is recommended to bring the air supply for the stove into the house using a 4 plastic pipe Where the pipe me...

Page 10: ...the Back with heat shields fitted twin wall insulated pipe see Fig 7 250mm 10 From the Back with heat shields fitted single wall pipe 350mm 14 From the Sides 550mm 213 4 From the Flue Pipe with heat s...

Page 11: ...appliance with the fuels likely to be used on the stove and warn them to use only the recommended fuels for the stove Advise the user what to do should smoke or fumes be emitted from the stove The cus...

Page 12: ...times Operate the stove only with the fuelling door closed except for re fuelling This stove has obtained HETAS Ltd approval for burning wood logs HETAS Approval does not cover the use of other fuels...

Page 13: ...air con trol fully as this will help to eliminate any smoke or fly ash resident in the combustion chamber Add fuel to fire close fire door and adjust the primary air con trol to the desired position...

Page 14: ...of usage The chimney can be cleaned through the stove depending on the flue configuration and the flue liner should be cleaned in accordance with manufacturer s instructions Always use a brush with p...

Page 15: ...epartment b Prepare occupants for immediate evacua tion c Close all openings into the stove d While awaiting the fire department watch for ignition to adjacent combustibles from over heated flue pipe...

Page 16: ...E DOOR 13886 4KW DOOR 17 AIR CONTROL ROD A4 AIR CONTROL ROD 18 FIRE FENCE LOG RETAINER 19 GRATE A4 CAST GRATE ASSY W 20 FLUE SPIGOT A4 COLLAR 21 DOOR GLASS FD9 22 FLUE BLANKING PLATE A4 04 REAR BLANK...

Reviews: