14
WARNING NOTE:
Properly installed, operated and maintained this
stove will not emit fumes into the dwelling.
Occasional fumes from the de-ashing and re-
fuelling may occur. However, persistent fume emis-
sion is potentially dangerous and must not be toler-
ated. If fume emission does persist, then the follow-
ing immediate action should be taken:
(a) Open doors and windows to ventilate room.
(b) Let the fire out or eject and safely dispose of
fuel from the stove.
(c) Check for flue or chimney blockage and clean if
required.
(d) Do not attempt to relight the fire until the cause
of the fume emission has been identified and
corrected. If necessary seek expert advice.
The most common cause of fume emission is flue-
way or chimney blockage. For your own safety
these must be kept clean at all times.
FIRE SAFETY
To provide reasonable fire safety, the following
should be given serious consideration.
1. Do not over fire the stove.
2. Over-firing will also damage the painted finish.
3. Install a smoke detector in the room.
4. A conveniently located class A fire extinguisher to
contend with small fires resulting from burning
embers.
5. A practical evacuation plan.
6. A plan to deal with a chimney fire as follows:-
(a) Notify the fire department.
(b) Prepare occupants for immediate evacua-
tion.
(c) Close all openings into the stove.
(d) While awaiting the fire department watch for
ignition to adjacent combustibles from over-
heated flue pipe or from embers or sparks
from the chimney.
CO ALARM
The fitting of CO Alarms in the same room as the
appliance is a compulsory requirement under cur-
rent Building Regulations. For ROI an additional CO
Alarm must be fitted either inside each bedroom or
within 5 metres of the bedroom door, refer to
Building Regulations Part J. Further guidance on the
installation of a carbon monoxide alarm is available
in BS EN 50292:2002 and from the alarm manufac-
turers instructions.
Provision of an alarm must not be considered a
substitute for either installing the appliance cor-
rectly or ensuring regular servicing and mainte-
nance of the appliance and chimney system.
WARNING:-
If the CO Alarm sounds unexpectedly:-
1. Open Doors and windows to ventilate the
room and then leave the premises.
2. Let the fire go out.
Fig.14
GLASS REPLACEMENT
a.
Open the door fully.
b.
Remove the four fixing screws and clips
(see Fig 14).
c.
Clean the glass recess in the door.
d.
Replace the adhesive thermal tape on the
back face of the door if damaged..
e.
Fit the glass in position and replace the four
corner clips & screws.
f.
Hand tighten the screws, turning back 1/4”
turn when hand tight.
g.
Replace glass only with ceramic glass.
Glass Fixing
Screws