9
HEAT RECOVERY VENTILATION
Where a stove is to be installed in a dwelling with
Heat Recovery Ventilation
(HRV) a number of
precautionary measures must be undertaken:
Where the product is to be installed with a
Mechanical Ventilation, the stove must be connect-
ed to an external air supply, The ductwork for the
external air supply must be no longer than 6 metres
and the air inlet terminal to the ductwork must have
a cross sectional area of at least 80cm
2
.
LOCATION
There are several conditions to be considered in
selecting a location for your Stanley Stove.
a. Position in the area to be heated, central
locations are usually best.
b. Allowances
for
proper
clearances
to
combustibles.
c. Allowances for proper clearances for mainte-
nance work.
From the Front
800mm (31
1/2
”)
From the Back (with heat shields
fitted & twin wall insulated pipe -
see Fig 7)
250mm (10”)
From the Back (with heat shields
fitted & single wall pipe)
350mm (14”)
From the Sides
550mm (21
3/4
”)
From the Flue Pipe (with heat
shields fitted & twin wall insulated
pipe - see Fig 7)
250mm (10”)
Mantle Clearance
760mm (30”)
Side Trim Clearance
450mm (18”)
Brick wall minimum clearance, but allow access
for controls and servicing.
CLEARANCES TO COMBUSTIBLES
Maintain at least the following clearances to all
combustible material:
FLOOR PROTECTION
When installing this heater on a combustible floor, a
floor protector consisting of a layer of non com-
bustible material at least 310mm thick covered with
“1/8 sheet metal” is required to cover the area under
the heater and extend at least 460mm at the front,
200mm to the sides & the rear. This will provide pro-
tection from sparks and embers which may fall out
from the door when stoking on refuelling. See Fig.8.
Fig.8
Fig.7
Vertical Heat
Shield
Back Heat
Shield
8”
8”
18”
8”