STOVE DIMENSIONS
WARNING:
DO NOT OBSTRUCT PRIMARY AIR SUPPLY TO THE STOVE
10
Note:
Dimensions stated are in millimetres unless otherwise stated and may be subject to a /- variation.
Fig.9
COMMISSIONING AND HANDOVER
On completion of the installation allow a suitable
period of time for any fire cement and mortar to dry
out, when a small fire may be lit and checked to
ensure the smoke and fumes are taken from the
stove up the chimney and emitted safely to the
atmosphere.
Do not run at full output for at least
24 hours.
Ensure that the operating instructions for the stove
are left with the customer. Ensure to advise the cus-
tomer on the correct use of the appliance with the
fuels likely to be used on the stove and warn them to
use only the recommended fuels for the stove.
Advise the user what to do should smoke or fumes
be emitted from the stove. The customer should be
warned to use a fireguard to BS 8432: 2010 in the
presence of children, aged and/or infirm persons.
OPERATION
Check that all dampers and catches are operating
correctly and ensure that all flue connections are
thoroughly sealed.
AIR CONTROLS
The stove has two independent air controls:
1.
The Primary Air Control Lever which controls
the primary air (See Fig 10). Pull out to open
& push in to close.
2.
The Secondary Air Control Lever which
controls the secondary air and air wash (See
Fig 10). Pull out to open & push in to close.
Note:
The controls may become hot when the stove is in
operation, use glove provided to adjust the controls
when the stove is hot.