Service Analyser Codes 

Pool Heat Pump

 

| Pg 28

 

 
 
Service Analyser Codes 

Code 

 

HP 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

OFF 

 
 
 
 
 
 
 

 

oC1, Sc1 

 
 
 

ot 

 

 

 

Problem 

– Action / Remedy 

 
Action / Remedy

: Make sure the water reaches the pool heat pump and the 

pool pump is completely filled to the rim. Otherwise: 
 

-

 

Fill the pool pump with  water and check to see if the pipes between the 
pool pump and the pool are watertight (there should be no air intake); 

-

 

Check the swimming pool and pool skimmer baskets and the drain at the 
bottom of the pool for obstructions; 

-

 

Check  the  filter  cartridges  for  obstructions  (wash  or  change  the 
cartridges, as the case may be); 

-

 

Insure  that  the  bypass  valves  are  in  the  correct  positions  so  that  the 
water flows adequately; 

-

 

Backwash sand filter (insure that there is a sufficient amount of sand and 
verify  that  it  does  not  have  to  be  changed.  Consult  a  swimming  pool 
specialist if necessary); 

-

 

Make sure the vacuum robot is disconnected so the water flows freely; 

-

 

If  you  have  a  two  speeds  pool  pump,  make  sure  that  it  is  set  at  the 
highest speed. 

 

Problem

:  Tthe  electronic  control  with  diagnostics  or  reversible  (XLR) 

electronic control with diagnostics is

 OFF

 or could be defective. 

 

Action / Press on the ON/OFF key 
 
 
  

 

 

 

 
Problem

: The water temperature probe has a loose connection or is faulty. 

The probe will need to be checked and replaced, if required. 

 
Action / Remedy

: Contact customer service. 

 
Problem

:  Water  temperature  is  higher  than  45  °C  (113  °F)  within  the  unit 

(this  code  is  only  displayed  on  the  electronic  control  with  diagnostics  and 
reversible (XLR) electronic control with diagnostics). 

 

 

Action / Remedy

-

 

Make sure the bypass valves are in the correct positions; 

-

 

Proceed  to  the  calibration  of  the  electronic  control  with  diagnostics  and 
reversible (XLR) electronic control with diagnostics. 

 

 

 

 

 

Problem - Action / Remedy 

 
Problem

:  Low  refrigerant  level  in  the  pool  heat  pump  or  the  low-pressure 

safety control is defective. 
 
Atmospheric conditions as well as the pool water temperature should not be 
below  the  minimum  operating  temperatures,  as  stated  below,  in  order  to 
obtain  efficiency  and  avoid codes from  appearing  on the electronic control 
temperature display.  These codes are not generally a problem with the pool 
heat pump at these conditions and are not covered under warranty. 
 
If  temperatures  are  below  the  minimum  temperatures  the  pool  heat  pump 
should not be operated and must be switched off. 

Code 

 

LP 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

HP 

 

32 °F (0 °C) 

43 °F (6 °C) 

52 °F (11 °C) 

50 °F (10 °C) 

65 °F (18 °C) 

65 °F (18 °C)

 

Atmospherics

 

conditions

 

must be above

 

Model

 

Pool water

 

temperature

 

must be above

 

Ultra 

Reversible (XLR) 

All others 

Action / Remedy

:

 

-

 

If the LP code is shown permanently, press 

ON/OFF

 before getting to the 

next step; 

 

-

 

Ensure  the  evaporator  is  clean. 

If  not,  switch  the  unit  OFF  from  the 

circuit  breaker 

(fuse)  and  use  a  garden  hose  to  lightly  clean  the 

evaporator.  Allow it to dry before re-starting the pool heat pump to avoid 
premature ice build up on the evaporator. 

 

-

 

Ensure installation instructions have been followed.  Improper installation, 
e.g. no air circulation, could lead to the pool heat pump continually going 
into LP mode and the installation will need to be corrected by the owner.  
This situation is not covered by the warranty. 

 

Problem

:  Low  water  circulation  in  the  unit  or  the  high-pressure  control  is 

defective.   
 
Note: The pool pump will stop functioning only if the internal time delay of the 
pool heat pump is being used. 
 

IMPORTANT

:  When  the  code  HP  is  permanently  displayed,  before 

performing the  steps  below  please press 

ON/OFF

  for the  electronic control 

with diagnostics and the reversible (XLR) electronic control with diagnostics. 

 

 

Summary of Contents for Ultra

Page 1: ...t Une installation inadéquate annulera la garantie Notice to Installer Avis à l installateur This manual contains important information about the installation operation and safe use of this product Once the product has been installed this manual must be given to the owner operator of this equipment Ce manuel contient des informations importantes sur l installation l exploitation et l utilisation s...

Page 2: ...___ Compressor Starts and Stops ____________ There Is Water Around the Pool Heat Pump _ Pool Heat Pump Has Ice Formed On the Evaporator Coil _________________ Pool Heat Pump Is Not Heating ___________ Analysis Chart ________________________ Circuit Breaker Trips ___________________ Pool Heat Pump Is Noisy ________________ The Temperature Shown on Pool Heat Pump Is Not the Same than the Pool Thermo...

Page 3: ...ded for proper operation and heating Please refer to the section Location on the following page IMPORTANT Usage of Chemical Products Never add liquid chlorine granular chlorine or slow dissolving tablets pucks into the skimmer basket This high concentration of chemicals should be avoided Water quality standards that must be strictly adhered to Warranty can be voided if not maintained within these ...

Page 4: ...ir is pulled through the evaporator coil and discharged through the top or front grill Clearances should be allowed in front and around the unit for unrestricted air discharge and service access See Figure 1 and Figure 2 Re circulation of cold discharged air back into the evaporator coil will greatly reduce the unit s heating capacity and efficiency Pool Heat Pump Pg 06 No obstruction above Pool H...

Page 5: ... MUST be installed between the pool heat pump and any automatic chlorinator to prevent highly chlorine concentrated water from flowing back to the pool heat pump when the pool pump is not running 2 Units that are located below the water level of the swimming pool may require the pressure switch to be adjusted This can be checked by the following method Switch ON the water pump and the pool heat pu...

Page 6: ... these systems may leak stray voltage and currents into the water causing severe electrolysis This dramatically shortens the life of the pool heat pump and will void the warranty NOTE Bonding to pool pump is not required for above ground pool pumps but all other equipment must be bonded Pool water temperature must be above Atmospheric conditions must be above Model Ultra Reversible XLR All others ...

Page 7: ...g back to the pool water temperature when all keys remain untouched for 5 seconds To change the temperature display from Fahrenheit F to Celsius C press the button C F The led below the F or C will be lit to indicate the current selection Note The pool heat pump will stop working when the programmed temperature is reached OPERATION OF YOUR POOL HEAT PUMP Pool Solar Blanket A pool solar blanket sho...

Page 8: ...e XLR Electronic Control with Diagnostics Functioning of your Electronic Control with Diagnostics and Reversible XLR Electronic Control with Diagnostics OPERATION OF YOUR POOL HEAT PUMP Temperature Calibration It is possible to have a temperature variation between the water in the swimming pool and the reading of the pool heat pump temperature probe sensor Example the water in the pool is 26 ºC 80...

Page 9: ... 70 F 21 C please adjust the bypass valve as shown Approx 60 of the water is circulating in the unit When the pool water temperature is between 70 F 21 C and 78 F 26 C please adjust the bypass valve as shown Approx 80 of the water is circulating in the unit When the pool water temperature is above 79 F 26 C please close the bypass valve as shown 100 of the water is circulating in the unit IMPORTAN...

Page 10: ...the pool heat pump s heat exchanger in preparation for winter 4 Once the piping is disconnected the pool heat pump s heat exchanger MUST be emptied the use of a water vacuum cleaner is strongly recommended or if you do not have this tool you can tilt the unit 75 until all the water is out 5 It is recommended that the pool heat pump s heat exchanger is rinsed out with a gentle water spray at the in...

Page 11: ...was condensation which is normal TROUBLESHOOTING Nothing Is Working but the Electronic Control Displays Digits or a Code 1 Identify the analyser code that the electronic control displays and refer to the section Service Analyser Codes 2 If the electronic control displays digits make sure that the electronic control is programmed correctly refer to the section Operation of your Pool Heat Pump and r...

Page 12: ...s free of debris and leaves 3 If the evaporator is dusty or dirty clean it with a light spray of water and allow it to dry do not use high pressure it may damage the evaporator fins 4 When the unit is dry you may switch it back ON from the circuit breaker 5 Ensure that the clearances around the unit are respected 6 When the unit has been switched ON ensure the fan motor is working fan blades will ...

Page 13: ...s coming from the pool heat pump and not from other equipment which will not be covered by the warranty e g noise coming from the bypass valve pool pump etc 3 An improper installation may cause this situation it will need to be corrected by the owner This situation is not covered by the warranty The Temperature Shown on the Pool Heat Pump Is Not the Same than the Pool Thermometer It is possible to...

Page 14: ...ure the pool pump is switched ON Press ON OFF to restart the pool heat pump On new installations ensure the installation instructions were respected Check that the pool water level is correct that the pool pump is filled with water to the rim and that water is flowing correctly through the pool pump to the pool heat pump Check swimming pool and pool pump skimmer baskets and the drain at the bottom...

Page 15: ...ics and reversible XLR electronic control with diagnostics Problem Action Remedy Problem Low refrigerant level in the pool heat pump or the low pressure safety control is defective Atmospheric conditions as well as the pool water temperature should not be below the minimum operating temperatures as stated below in order to obtain efficiency and avoid codes from appearing on the electronic control ...

Page 16: ...tion stated in this section Warranty will only cover manufacturing defects All service call requests which are not of this nature must be paid by the purchaser to the service company authorized by Waterco Warranty service is to be completed by an authorized Service Center authorized by Waterco Where applicable in home service will be made available only in areas where a contracted service provider...

Reviews: