I pg 20
Pool Heat Pump
Protection devices
The integrity and performance of your pool heat pump and its components are protected
by internal safety controls. In normal use, your Waterco unit should never reach the thermal
protection level. However, if it should happen, you should identify the stated code on the
temparature display and refer to Service Analyser codes.
Adjustment Of The Bypass Valves
The adjustment may vary according to pool pump size and ambient temperatures.
ATTENTION: IT IS VERY IMPORTANT THAT THE BYPASS VALVES ARE SET AS DESCRIBED
BELOW FOR THE CORRECT FUNCTION OF YOUR POOL HEAT PUMP
When the pool water
temperature is
between 65°F (18°C) and 70°F
(21°C) please adjust the bypass
valve as shown. Approx. 60%
of the water is circulating in
the unit.
OPEN
VALVE POSITION
HEAT
PUMP
INLET
OULET
OPEN
VALVE POSITION
HEAT
PUMP
INLET
OULET
When the pool water
temperature is between
70°F (21°C) and 78°F (26°C)
please adjust the bypass valve
as shown. Approx. 80% of the
water is circulating in the unit.
VALVE POSITION
CLOSED
HEAT
PUMP
INLET
OULET
When the pool water
temperature is above
79°F (26°C) please close the
bypass valve
as shown. 100% of the water
is circulating in the unit.