WATANABE WPMZ-5 Quick Instruction Manual Download Page 8

 

 

MODEL WPMZ-5-□□□-□□-□□□                                                                                 

 

8/12 

 

                                                                                                                                                                                                 

IM-0834-03 

10-2. 

 

AVAILABLE UNITS 

     

The WPMZ has selectable 62 units. 

Unit 

μA,mA,A,kA,μV,mV,V,kV,VA,W,kW,MW, 

μm,mm,cm,m,Ω,kΩ,MΩ,g,kg,N,kN,MN, 

Pa,kPa,MPa,hPa,J,kJ,MJ,Hz,kHz,MHz,m

3

mm/s,mm/min,cm/min, m/s,m/min,m/h,m/s

2

m

3

/s,m

3

/min,m

3

/h,kg/h,kg/m

2

,kg/m

3

,N/m

2

ℓ,ℓ/s,ℓ/min,ℓ/h,%,%

0

,%RH,

pH,ppm,rpm,t,inch

 

 

10-3. 

 

SETTING OPERATION 

Setting procedure is same as “

8. BASIC OPERATIONS FOR 

SETTING DISPLAY

”. Operate in the track of SETTING DIPLAY. 

 

11. 

 

COMPARATIVE OUTPUT FUNCTION 

     

Settings of comparative output functions needs 10 parameters to 

   

  set for each output. 

     

The following describe only main setting parameters and refer to 

   

  detailed manual which can be downloaded from our homepage for 

   

  other parameters.   

 

11-1. 

 

LOCATIONS OF  PARAMETERS FOR COMPARATIVE 

OUTPUT FUNCTION SETTING 

1st layer 

2nd layer   

3rd layer 

4. Output 

settings 

Comparative output AL1 

Comparative output AL2

Comparative output AL3

 

Comparative output AL4

 

pattern select 

output source display 

value 

camparison mode 

compare ON condition 

compare judgement value 

campare ON delay 

campare OFF delay 

output mode 

output logic 

compare ON background 

color 

     

*Refer to “7. SETTING LAYER OVERVIEW” 

 

11-2. 

 

SETTING OF OUTPUT SOURCE DISPLAY VALUE 

 

  Comparative outputs AL1-AL4 are settable independently and 

 

  they have no magnitude relationship. 

 

  For example, instantaneous measured value of Ach is assigned to 

 

  AL1, instantaneous measured value of Bch is assigned to AL2   

    and instantaneous calculate value is assigned to AL3,4 and so on. 
    Every display item can be freely assigned to comparative 
    outputs. 
    Setting procedure is same as “8. BASIC OPERATIONS FOR 
    SETTING DISPLAYS”. Operate in the track of the procedure of 
    SETTING DISPLAYS. 

Caution:  COM  (emitter)  terminal  is  common  for  AL1-AL4    in 

open-collector  output  products.  Each  AL1&2,  AL3&4  have 

common terminal in relay ouput products. 

 

11-3. 

 

COMPARISON JUDGEMENT VALUE 

The comparison judgement value is a threshold value to judge. 
Although, the setting procedure is same as “8. BASIC 
OPERATIONS FOR SETTING DISPLAY”, comparison 
judgement values need the settings of numerical values. 
Therefore, its procedure is shown below. 

*

The following is an explanation for the compare mode of “Level 

judgement ”. 

 

Level judgement action

 

Comparative 

Output 

Comparison 

type 

Comparison 

formula 

judgement 

result 

AL1 

alarm when 

over 

display value

AL1 

judgement value 

AL1 ON 

AL2 

alarm when 

over 

display value

AL2   

judgement value 

AL2 ON 

AL3 

alarm when 

under 

display value

AL3 

  judgement value 

AL3 ON 

AL4 

alarm when 

under 

display value

AL4 

  judgement value 

AL4 ON 

       

*

Refer to “17. SPECIFICATIONS –output specifications 
[comparative output]” 

 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

(Measurement display)

ENTER

Moves to setting display(1st layer)by 

MENU key.

ENTER

Moves to 2nd layer by right 

arrow key.

Moves to 4th 

layer by right 

arrow key.

Moves to numerical value 

setting display by ENTER key.

Selects numerical 

value by arrow keys 

(up/down/left/right)

Registers selected numerical 

value by ENTER key.

Returns to 3rd 

layer by left 

arrow key.

Stores selected parameters 

and returns measurement 

display by MENU key.

1st layer

3rd layer

MENU

1st layer

Moves to 3rd 

layer by right 

arrow key.

2nd layer

3rd layer

4th layer

4th layer(numerical value setting)

4th layer

3rd layer

MENU

Returns to 2nd layer by 

left arrow key.

Moves to other setting items 
by up/down arrow keys.

4th layer(numerical value setting)

Moves to setting 

“2.output” by down 

arrow keys.

Moves to “Threshold 

value” by down arrow keys.

AL1 Hysteresis

Display value

AL1 Judgement value(Over)

AL2 Hysteresis

AL2 Judgement value(Over)

AL3 Hysteresis
AL3 Judgement value(Under)

AL4 Hysteresis
AL4 Judgement value(Under)

AL2

AL1

AL3

AL4

J

ud

ge

m

en

re

su

lt

Summary of Contents for WPMZ-5

Page 1: ...Do not wire the power supply line input signal lines and output signal lines near noise sources or relay drive lines 3 Bundling or containing in a same duct with lines including noises might cause malfunctions 4 The WPMZ becomes available functionally right after power activation but requires 30 minutes warming to satisfy all performance requirements Note The inputs A channel and B channel may be ...

Page 2: ...NE Ach Line driver input terminal 16 GND Ach GND input terminal 17 EXC Ach sensor power output terminal 18 EXC Ach sensor power output terminal 19 20 NC No connection Non usable for a relay terminal B channel line driver input terminal name description 21 LINE Bch Line driver input terminal 22 LINE Bch Line driver input terminal 23 GND Bch GND input terminal 24 EXC Bch sensor power output terminal...

Page 3: ...tive Indicates comparative output reset function an external control function is effective Indicates measurement inhibit function an external control function is effective Indicates display hold function an external control function is effective Indicates maximum value or minimum value hold function an external control function is effective 5 2 2 Key Operation Icons On The Setting Display Key oper...

Page 4: ...imes 8times 9times Set number of moving average Instantaneous value simple average InsSimpleAve None None 2 times 4 times 8 times 16 times 32 times 64 times 128 times 256 times Set number of simple average for internal sampling 10ms Instantaneous value display step InsDispStep None None 5steps 10steps Setting of steps of display If set to 5steps displayed only 0 or 5 on LSB WPMZ 5 L Pulse Input A ...

Page 5: ...0bps 19200bps 38400bps Set baudrate Data length DataLength 8bit 7bit 8bit Set data character length Parity Parity None None Even Odd Set parity bit Stop bit Stopbit 1bit 1bit 2bit Set stop bit length Delimiter Delimiter CR CR CR LF Set delimiter type 3 Display Display Select Measure select MeasureSelect 1input InsA 2inputs InsA InsB InsA InsB InsCalc InsA InsB InsCalc A B InsA Comp InsB Comp InsCa...

Page 6: ...ting items If the arrow key LEFT is pushed the display returns to the 2nd layer On the 3rd layer by pushing the MENU key the display returns to the measurement display By moving the cursor with arrow key UP DOWN select a setting item If the arrow key LEFT is pushed the display returns to the 2nd layer At the selected setting item by pushing arrow key RIGHT the display moves to the 4th layer settin...

Page 7: ...r 1 pulse as instantaneous display coefficient Although instantaneous flow rate will be displayed in ℓ min the rating of the sensor is 7 5 mℓ Pulse it should be converted to 7 5 10 3 ℓ Pulse Set the Instantaneous display factor as 7 50000 10 3 Displayed unit is ℓ min therefore select Minute as the instantaneous unit time By instantaneous decimal point position set the number of digits after the de...

Page 8: ...common for AL1 AL4 in open collector output products Each AL1 2 AL3 4 have common terminal in relay ouput products 11 3 COMPARISON JUDGEMENT VALUE The comparison judgement value is a threshold value to judge Although the setting procedure is same as 8 BASIC OPERATIONS FOR SETTING DISPLAY comparison judgement values need the settings of numerical values Therefore its procedure is shown below The fo...

Page 9: ...d Bch 12 7 PATTERN SELECT FUNCTION The pattern select function is the function which switches the pattern number to use for measurement By using pattern select 1 3 Up to 8 patterns can be switched Function Name Selected pattern No pattern No in use 1 2 3 4 5 6 7 8 Pattern select1 Open Short Open Short Open Short Open Short Pattern select2 Open Open Short Short Open Open Short Short Pattern select3...

Page 10: ...ys Please refer to 14 1 Locations of parameters for initialize 14 3 2 Initializing To User Defaults By executing to initialize to user defaults current setting values are replaced by user defaults Steps for the initialize operation are same as 14 2 Initializing to the factory defaults Operate the WPMZ according to the setting displays Please refer to 14 1 Locations of parameters for initialize 15 ...

Page 11: ... structure IP66 front Installation environment indoor use Rated altitude up to 2000m Transient overvoltage Ⅱ Measurement category Ⅱ Pollution degree 2 Conformed EN standard EN61326 1 EMS industrial electromagnetic environment EMI Class A Applicable to line length only under 30m EN61010 1 EN50581 Material of enclosure polycarbonate PC black UL94V 0 Input Specifications Pulse input instantaneous mea...

Page 12: ...ay value AL2 zone upper limit or AL2 zone lower limit display value AL2 display value AL3 zone upper limit or AL3 zone lower limit display value AL3 display value AL4 zone upper limit or AL4 zone lower limit display value AL4 Conversion method D A conversion method Resolution capability Equivalent of 13bit Scaling Digital scaling Output objective Response speed Specification for each output An ite...

Reviews: