MODEL WPMZ-5-□□□-□□-□□□
4/12
IM-0834-03
BASIC OPERATIONS, SETTINGS
6.
BASIC OPERATIONS OF MEASUREMENT DISPLAY
During measurement mode, the following key operations can be done.
①
By pushing the “DISP key” in the measurement mode, the display can be switched to others which are selected in “display select”.
②
By pushing the “MENU key” in the measurement mode, the display moves to the setting display.
Alternatively, by pushing the “MENU key” in the setting display, the display returns to the measurement display
③
By pushing the “FUNC key” in the measurement mode, the display moves to the shortcut entry display.
Alternatively, by pushing the “FUNC key” in the shortcut entry display, the display returns to the measurement display.
④
During measurement, by holding down the “arrow key” in 1 second, the shortcut function registered to the key will be executed.
On this occasion, the display has no change.
7.
SETTING LAYER OVERVIEW
The setting menus of the WPMZ which are represented by key words and have layers, therefore desired setting menu can be selected
accurately. The layers consist of 1st layer to 4th layer (Only custom unit setting has the 5th layer).
Please refer to “
8. BASIC OPERATION OF SETTING DISPLAY
” about how to set up.
1st layer
Large categories
2nd layer
Small categories
3rd layer (setting items)
4th layer (setting contents)
Remarks
name of item
Character strings on
display
(abbreviated form)
Initial values
Settable variables
1.Input
(WPMZ-5-
□
P
□
)
Pulse input A
Pulse input B
Pattern select
PatternSelect
Pattern1(or pattern No.
in use)
Pattern1/ Pattern 2/ Pattern 3/ Pattern 4/ Pattern
5/ Pattern 6/ Pattern 7/ Pattern 8
Select pattern No. to set.
Input type
InputType
OpenCollector
OpenCollector/Logic/ZeroCross/2Wire
Select input signal type
Input filter
InputFilter
None
None/30Hz/1.5kHz/15kHz
Select analog input filters
Sensor power
SensorPower
12V
12V/24V
Switch Sensor power voltage
Instantaneous value
display coefficient
InsDispCoef
1.00000×10
0
0.00000 to 9.99999×10
-9
~
9
For scaling setting of instantaneous value display,
multiply frequency by instantaneous coefficient and
unit time.
Instantaneous unit
time
InsUnitTime
Sec
Sec/Min/Hour
Instantaneous value
decimal point position
InsDecPoint
######
(No decimal point)
######/ #####.#/ ####.##/ ###.###/ ##.####/
#.#####
Set number of digits after decimal point
Instantaneous value
display unit
InsDispUnit
None
None/select from 62 units (See 6-2)/custom unit
Refer to detailed instruction manual about custom
unit
Instantaneous value
auto zero
InsAutoZero
0.00
0.00 to 99.99sec
Displays 0 if no pulse input over more than setting
time
Instantaneous value
moving average
InsMoveAve
None
None/2times/3times /4times /5times /6times
/7times /8times / 9times
Set number of moving average.
Instantaneous
value simple average
InsSimpleAve
None
None/2 times /4 times /8 times /16 times /32 times
/64 times /128 times /256 times
Set number of simple average for internal sampling
(10ms)
Instantaneous value
display step
InsDispStep
None
None/5steps/10steps
Setting of steps of display
(
If set to 5steps, displayed
only 0 or 5 on LSB
)
(WPMZ-5-
□
L
□
)
Pulse Input A
Pulse Input B
Pattern select
PatternSelect
Pattern1(or pattern No.
in use)
Pattern1/ Pattern 2/ Pattern 3/ Pattern 4/ Pattern
5/ Pattern 6/ Pattern 7/ Pattern 8
Select pattern No. to set.
Input Type
InputType
Line driver
Line driver
Only line driver
Input filter
InputFilter
None
None
None analog filters
Sensor Power
SensorPower
5V
5V
Sensor power is 5V only
Instantaneous value
display Coefficient
InsDispCoef
1.00000×10
0
0.00000 to 9.99999×10
-9
~
9
For scaling setting of instantaneous value display,
multiply frequency by instantaneous coefficient and
unit time.
Instantaneous value
unit time
InsUnitTime
Sec
Sec/Min/Hour
Instantaneous value
decimal point position
InsDecPoint
######
(No decimal point)
######/ #####
.
#/ ####
.
##/ ###
.
###/
##
.
####/ #.#####
Set number of digits after decimal point
Instantaneous value
display unit
InsDispUnit
None
None/select from 62 units (See 6-2)/custom unit
Refer to detailed instruction manual about custom
unit
Instantaneous value
auto zero
InsAutoZero
0.00
0.00 to 99.99 sec
Displays 0 if no pulse input over more than setting
time
Instantaneous value
moving average
InsMoveAve
None
None/2times/3times /4times /5times /6times
/7times /8times / 9times
Set number of moving average for analog inputs
Instantaneous
value simple average
InsSimpleAve
None
None/2 times /4 times /8 times /16 times /32 times
/64 times /128 times /256 times
Set number of simple average
Instantaneous value
display step
InsDispStep
None
None/5steps/10steps
Setting of steps of display
(
If set to 5steps, displayed
only 0 or 5 on LSB
)
2 input
calculation
Pattern select
PatternSelect
Pattern1(or pattern No.
in use)
Pattern1/ Pattern 2/ Pattern 3/ Pattern 4/ Pattern
5/ Pattern 6/ Pattern 7/ Pattern 8
Select pattern No. to set.
Expression for
instantaneous value
InsExpression
None
None/ (B/A)*100 / (B/A-1)*100 /B-A /
(B/(A+B))*100 / A+B
Select expression for calculation of instantaneous
value.
Instantaneous value
decimal point position
InsDecPoint
######
(No decimal point)
######/ #####.#/ ####.##/ ###.###/ ##.####/
#.#####
Set number of digits after decimal point
Instantaneous value
display unit
InsDispUnit
None
None/select from 62 units (See 6-2)/custom unit
Refer to detailed instruction manual about custom
unit
Instantaneous value
display step
InsDispStep
None
None/5steps/10steps
Setting of steps of display
(
If set to 5steps, displayed
only 0 or 5 on LSB
)
MENU
DISP
DISP
DISP
FUNC
Execute a shortcut function
*The function is valid, only if the
shortcut function is assigned to
the arrow key.
(Hold down 2 sec.)
or
or
or
①
①
①
①
②
③
④
DISP
MENU
FUNC