background image

22

   

Warner Electric • 800-825-9050

P-0257-WE • 819-9027

Using a voltmeter, check the DC voltage at the brake terminals as follows: Slowly 
raise the dancer and observe that the voltage decreases then slowly lower the 
dancer and observe that the voltage increases. If the voltage indications are the 
opposite, reverse the sensor leads at terminals 5 and 7 of the control (see sensor 
wiring).
If no voltage change occurs, check sensor cable connections (check pivot point 
coupling: connection if MCS-605-1 or TCS-605-5 sensor is used).
If no voltage change occurs, be sure that the brake wires are not grounded to 
machine.

Symptom C: Dancer moves to and remains at upper limit after operating In a normal running position for a 
period of time.

Probable Cause

Suggested Solution

Incorrect Dancer Position setting

Adjust dancer position setting until dancer moved to normal running position.

Dancer pivot point sensor coupling has slipped If dancer position adjustment lowers the arm near its normal running position, 

realign pivot point sensor (see sensor mounting).

Faulty P.C. Board

With dancer position and gain at minimum setting, check that the voltage on the 
brake terminal reduces to less than two volts as the dancer arm is raised. If voltage 
does not reduce to less than two volts, replace printed circuit board assembly.

(Problem occurs near roll core only) Residual 
torque of the unwind stand exceeds the 
minimum torque allowable for the application.

With dancer position and gain at minimum setting, check that the DC voltage 
at the brake terminals reduces to 0 and reverses polarity as the dancer arm is 
slowly raised. If the voltage reduces and reverses polarity, check to be sure that 
the brake is in good operating condition and properly installed (see tension brake 
maintenance-torque loss). Also check to be sure that the unwind stand friction 
is not excessive for the application. Check the brake selection procedure to be 
sure the brake being used does not exceed the minimum allowable torques, if the 
voltage did reduce to zero but did not reverse polarity, adjustment of the antiresidual 
may be necessary, If adjustment of the antiresidual does not cause the brake 
voltage to reverse polarity in the off state, replace the PC Board Assembly.

Symptom D: Dancer moves erratically - appears to hunt or oscillate.

Probable Cause

Suggested Solution

Incorrect Dancer Gain setting

Adjust dancer gain setting CCW until dancer stops hunting.

Nonuniform system friction

If the hunting coincides with each revolution of the web parent roll, check faulty 
bearings or mismounted brake.

Improperly installed sensor

When an MCS-605-1 Sensor is being used, check to be sure the index mark on the 
sensor shaft is aligned with the index mark on the sensor body when the dancer 
is at the mid-travel position. Also, be sure there is no lag between the movement 
of the dancer pivot point and the shaft of the sensor - the sensor shaft must move 
when the dancer pivot moves. With dancer centered, voltage at terminals 6 and 7 
should be 7.5 VDC ±0.1 VDC (refer to the sensor mounting section).

Loose or faulty sensor and cable assembly.

Check to be sure that all connections to the control terminal block and the brake 
wire connections are secure. Check electrical connector at sensor to be sure it is 
not loose. Using a DC voltmeter connected between control terminals 6 and 7, 
check to be sure the voltage variation is smooth as the dancer is slowly moved 
through its travel limits. If the voltage variation is not relatively smooth, either the 
sensor or cable assembly is faulty. To isolate the fault to the cable or the sensor, 
turn off power and disconnect the cable from the sensor and connect an ohmmeter 
between the middle pin and one of the remaining pins on the sensor receptable. 
The resistance indication should vary smoothly as the dancers moved through 
its travel limits. If the indication is erratic, the sensor should be replaced; if the 
indication is not erratic, the cable assembly should be replaced. If above steps 
seem normal, recheck dancer arm length (most applications require a dancer arm at 
least 12” long).

Summary of Contents for MCS-204

Page 1: ...Tension Control System MCS 166 MCS 203 MCS 204 Installation Operation Instructions P 0257 WE 819 9027...

Page 2: ...tem Troubleshooting MCS 166 MCS 203 21 22 MCS 166 MCS 204 23 Replacement Parts Listing 24 Listing of Figures and Illustrations 24 Notes Installation must be made in accordance with the instructions fo...

Page 3: ...motely by external potentiometer voltage input or current loop input The MCS 605 1 or TCS 605 5 Pivot Point Sensors provide the dancer position signal to the MCS 203 Dancer Control The MCS 605 1 is co...

Page 4: ...correspond to minimum output level Torque Adjust Span Provides for either manual adjust or span adjustment when in all other modes of operation General Information Control chassis must be considered...

Page 5: ...0 bolts c Apply the terminal strip label supplied with the control logic module to the PC Board as shown in Figure 2 page 6 CAUTION Be sure to apply the label in the proper position with the brake ter...

Page 6: ...r 4 13 64 mounting holes for each housing to provide clearance for the 10 mounting studs 4 Slide the housing assemblies into the mounting panel cutouts Securely fasten the housings to the mounting pan...

Page 7: ...shaft and pin are aligned and separated by 5 16 6 While holding the sensor and bracket in this position mark the centers of the bracket holes on the machine 7 Drill and tap three 3 holes for 8 32 scr...

Page 8: ...tation as viewed from the connector end of the pivot point sensor CW a For CW rotation connect sensor wires as follows Black to Terminal 5 green to Terminal 6 red to Terminal 7 Shield lead should be c...

Page 9: ...Warner Electric 800 825 9050 P 0257 WE 819 9027 9 Figure 7 MCS 166 MCS 203 Wiring Single Brake Figure 8 MCS 166 MCS 203 Wiring Dual Brakes...

Page 10: ...moving the roll follower pot toward the core will decrease voltage at terminal 6 c Voltage Source Input Connect side of external voltage source to terminal 6 and side or common of external voltage so...

Page 11: ...ont housings if either wall or shelf mounting is used Secure the latches If shelf mounting is used secure the housings with the four 4 bolts for each section 8 Do not insert the control modules at thi...

Page 12: ...12 Warner Electric 800 825 9050 P 0257 WE 819 9027 Figure 11 MCS 204 Input Configuration Figure 12 Analog Photoelectric Roll Follower Wiring...

Page 13: ...ide to side until the connectors mate but do not apply excessive force NEW STYLE UNITS WITH RIBBON CABLES Pull the ribbon cable forward so that the connector end is in front of the housing assembly Fa...

Page 14: ...rify that power is on 2 Start the machine and draw material 3 After the Dancer has stabilized adjust the front panel Dancer Position potentiometer for the desired dancer running position 4 If the syst...

Page 15: ...r response is not achieved with R16 at maximum CW setting the next higher differentiator response range should be used CAUTION When switching to higher response ranges R16 should be set full CCW Facto...

Page 16: ...16 Warner Electric 800 825 9050 P 0257 WE 819 9027 Figure 13 Control Adjustment Locations MCS 166 MCS 203...

Page 17: ...to side until the connectors mate but do not apply excessive force NEW STYLE UNITS WITH RIBBON CABLES Pull the ribbon cable forward so that the connector end is in front of the housing assembly Faste...

Page 18: ...eter through front panel so the 0 100 indicator illuminates This is a true zero output to the brake c Now rotate the torque span potentiometer toward its maximum setting As the pot is turned the 0 100...

Page 19: ...h corresponds to the exact center of the roll shaft Adjust the roll follower potentiometer to provide a DC input reading of 0 5 VDC 0 1 VDC d Remove the meter from the follower potentiometer and conne...

Page 20: ...20 Warner Electric 800 825 9050 P 0257 WE 819 9027 Figure 14 Control Adjustment Locations MCS 166 MCS 204...

Page 21: ...ck to be sure lead wires to the brake are at the brake terminals 1 and 2 of the control Check to see if sensor is connected Using a voltmeter check for approximately 1 8 to 28 VDC between the brake te...

Page 22: ...does not exceed the minimum allowable torques if the voltage did reduce to zero but did not reverse polarity adjustment of the antiresidual may be necessary If adjustment of the antiresidual does not...

Page 23: ...does not have the torque capacity required for the application Verify that the correct brake was selected by repeating the selection procedure Brake is not releasing as input level decreases Check th...

Page 24: ...23 Rear P C Board Assy MCS 204 W S end 6910 101 021 Fuse 3 Amp 250 Volt Fast Acting 458 8001 006 MCS 605 1 Pivot Point Sensor Single Turn 7330 448 002 TCS 605 5 Pivot Point Sensor 5 Turn 7330 448 003...

Reviews: