paGE 34
© 2014 OJ Electronics A/S
Sensor Calibration
This option allows you to calibrate the room sensor .
Calibration is only possible for the room sensor and only if “Room/Floor Limit” has
been chosen under “
Sensor application
” .
If the temperature reading differs from the actual room temperature (measured with
a thermometer) you can calibrate the sensor with +/- 10°C in steps of 0 .5°C in the
following way:
1 . Tap the “
menu
” button on the home screen .
Then tap the “
Engineer Settings
” button .
2 . Scroll down and tap the “
Sensor calibration
” button .
3 . Confirm that you want to calibrate the sensor with “
√
” or cancel with “X” .
4 . If “
√
” is chosen, you must then offset the thermostat to reflect the room tempera-
ture actually measured .
5 . Use the “
up arrow
” or “
Down arrow
” button to set the measured room tem-
perature .
6 . Confirm the value with “
oK
” . A confirmation screen will be displayed briefly .
7 . The thermostat will automatically return to “
Engineer Settings
” .