Installation step 4
If the cable does not pass
either test, DO NOT TILE.
Call the technical helpline
on 888-927-6333
Completely disconnect
the cable prior to and
during tiling.
IMPORTANT! Test the cable
Before tiling, ensure that the cable is working properly
by using the method described on page 16.
Test b
Test the probe wire:
Temperature sensor wire must be verified before and
after installation. For probe resistances, refer to the
thermostat instructions.
Install Warmup
®
Thermostat and floor probe.
Although the Warmup
®
system is designed to be installed by any competent do it yourselfer,
only a qualified electrician should undertake the wiring and connecting of the cable to a
thermostat. This is to safeguard against the risk of personal injury and to ensure that any
installation complies with National and local codes.
Install the Warmup
®
Thermostat.
Instructions for the fitting of the Warmup® Thermostat can be found
inside the thermostat box.
Each cable has one unheated lead. The unheated lead
consists of one white wire (neutral), one bare copper wire
(protective ground) and one black wire (live). Please review
the information on pages 7 through 9 before proceeding.
The bare copper (protective ground) wire leading from the
unheated lead should be connected to the ground leading
from the power supply.
Floor probe location
The floor probe wire for the Warmup thermostat will be
approximately 15 feet long.
The end of the wire contains a capped sensor that should
be centered between two heating cable at least 12” into the
heated area. At no time should the probe wire cross the
heating cable.
Ensure that safety labels contained within this manual are placed by the breaker box and
near the control as described.
22
A
Install the Warmup
Thermostat
and floor probe.