background image

15

“Beware of Using a  

Continuity Checker!”

Our smaller Heating Rolls have a high Ohm resistance 

and some continuity checkers do not send enough 

current to get completely through the wire and emit 

the noise or light that affirms proper continuity. If your 

instrument cannot function on a small Heating Roll, 

please use a digital Ohm meter.

Electrical Fault-Finding

Once the system has been turned off and made safe, 

have a suitably qualified person:

1.  Ensure all wires have been connected as per the 

wiring diagrams.

2.  Make sure multiple rolls have been wired in parallel 

with  all leads returning to the thermostat and not 

hooked to each other in series.

3.  Confirm that control devices are receiving correct 

voltage.

Use a well calibrated digital Ohm meter with good 

batteries. The Ohm resistance level of each Heating Roll 

should be checked and the reading compared with the 

resistance that was recorded during installation on the 

corresponding UL label(s) (located on the circuit breaker 

box) and in the log on Page 17 of this Manual. If your 

reading is not within the 15%+/- range from the original 

reading, the roll may be damaged in some way. If you get 

zero across the core this indicates an open or short circuit 

beneath the finished flooring. The electrical contractor 

must locate the point of break or short, in coordination 

with the Technical Services Department of WarmlyYours.

com.

Locating a Break or a Short

If  your  installation  is  complete,  all  wiring  connections 

have  been  verified  to  be  correct,  including  grounding  of 

the system, you have checked the sensor wire for proper 

Ohms  reading,  and  you  suspect  the  system  is  still  not 

working;  you  need  to  determine  if  there  is  a  break  or  a 

short under the floor.

Checking for Breaks

The  Ohm  resistance  of  each  roll  should  be  measured 

across the core wires. 

Make sure the probes of the Ohm meter do not touch the 

sheath  wire.  Make  sure  you  do  not  touch  either  of  the 

probe ends with your fingers, or the meter will be reading 

your internal body resistance.

Make sure your Ohm meter is set on the proper scale (0-

to-  200  for  Heating  Rolls,  or  0-to-20,000  for  the  sensor 

wire). Your Ohm resistance readings should come within 

15% (plus or minus) of the original measurement indicated 

by the factory on the UL label.

If your Ohm reading is within 15% of what it should be, 

there is no break. However, you still need to check for an 

electrical short.

If your Ohm reading is lower (outside the 15% range), but 

there  is  clearly  some  continuity,  check  your  Ohm  meter 

and your batteries. If these are good, there is a possibility 

that you have several electrical shorts.

Infinity Ohm Reading?

If  you  have  absolutely  no  reading  (=  infinity  on  your 

meter), and you are sure you adjusted the setting of the 

Ohm meter to the correct reading range (0-to-200 for the 

Heating Rolls, or 0-to-20,000 for the sensor wire), then you 

have a break (= total cut) in the conductor.

Checking for Electrical Short

In some rare occasions an installation may have suffered 

from a high pressure point that broke the insulation between 

the core conductor and the multi-stranded sheath. Such an 

opening in the insulation layer can create an electrical short, 

even though the Ohm reading from the white conductor to 

the yellow or red conductor is normal and does not indicate 

any circuit break. In these rare occasions a continuity test 

will  show  continuity  between  the  one  or  both  of  the  core 

conductors and the sheath wire.

There  should  be  no  continuity  (=“  infinite”  resistance 

reading, not zero) between the conductors and the sheath. 

If  your  instrument  reveals  continuity  between  the  core 

conductor and the sheath, there is a short in the circuit.

 

Electrician’s Guide – Trouble Shooting

Summary of Contents for TempZone

Page 1: ...1 1 Free Design Service 24 7 Installation Support No Nonsense Warranty 800 875 5285 www WarmlyYours com Installation Manual for your TempZone Electric Radiant Floor Heating System Twin Conductor...

Page 2: ...ted surface temperatures and lower energy usage The floor will have the capacity to warm to a comfortable temperature and in some cases can be employed as the primary heat source for that room Securin...

Page 3: ...Electrical Housing Boxes Switch Plates All control devices except a Relay Contactor fit into a double gang box If a double gang box is used it will need to be fitted with a single gang mud ring We str...

Page 4: ...to continue in a new direction See Page 5 for full details on how to execute turns F Free Form Space Indicates a length of Fiberglass Mesh that needs to be removed and separated from the Heating Eleme...

Page 5: ...re a Relay Contactor or Power Module s in addition to the control device to operate properly The Relay or the Power Modules may be located in the same vicinity as the control device If your system wil...

Page 6: ...is indicated on the Installation Plan by an arc with an arrowhead By examining the relationship between two panels you will determine the type of turn needed Free Form Free form spaces are filled with...

Page 7: ...Mesh sits on top of the Heating Element Working around Obstacles Special circumstances will require the Heating Element to circumvent an obstacle The released Heating Element is not needed to fill an...

Page 8: ...hold the wires onto the probes with your fingers A digital meter is easier to use and strongly recommended It is wise to verify that the batteries of the Ohmmeter are good Set your Ohmmeter to measur...

Page 9: ...lack Red Copper Ground Black Lead THERMOSTAT 1 2 3 4 5 C O INDIA Made by Thermopads Pvt Ltd for WarmlyYours com Inc ENREGISTRE LISTED C US RADIANT HEATING PANEL UNIT UNITE DE PLANCHER CHAUFFANT ELECTR...

Page 10: ...the Mudbed in the thin set used to adhere the tiles It is advised to prepare the subfloor as you would for any conventional installation along the Tile Council of America Guidelines Once installed ove...

Page 11: ...suitable glue or cement based adhesive or thinset mortar to adhere it to the slab If installing in a wet location ensure the slope of the mortar bed is maintained to direct water to the drain pipe Not...

Page 12: ...henever possible 2 Set tiles as recommended TIP Remove excess thin set that may ooze up between the grout joints with a wet rag toothbrush or sponge while installing the tile in preparation for a clea...

Page 13: ...n the UL label and on the installation plan The Ohms readings should be within a 15 variance of the Ohm value specified on the UL tag Measure the continuity between core wire and ground wire The readi...

Page 14: ...ply the Flooring Adhesive glue 1 Apply manufacturer s recommended adhesive as per flooring installation instructions Install Laminate Engineered Wood Flooring 1 Install laminate or engineered wood flo...

Page 15: ...anty cards Using a hot glue gun secure the cold lead to the mortar bed and over the shower curb In order to minimize tension on the cold lead use an S formation to bring the cold lead over the shower...

Page 16: ...Ohm resistance of each roll should be measured across the core wires Make sure the probes of the Ohm meter do not touch the sheath wire Make sure you do not touch either of the probe ends with your fi...

Page 17: ...If a sensor is used indicate its location on the plan The electrician should put the code labels UL from any Heating Roll used in a convenient place such as the circuit breaker box The labels should h...

Page 18: ...must be electrically grounded and protected by a GFI Ground Fault Interrupter 4 The installation must comply with all national and local electrical and building codes as well as any other applicable...

Page 19: ...INESS REPLY MAIL FIRST CLASS MAIL PERMIT NO 77 LONG GROVE IL WarmlyYours Inc 590 Telser Rd Ste B Lake Zurich IL 60047 NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES POSTAGE WILL BE PAID BY ADDRES...

Reviews: