Connecting Horizontal Hermetic Flue Set to the Combi
Since your combi is a hermetic model, it takes the used air from
outsideand discharges
Total length of hermetic flue set should not exceed 5 m with single
bend horizontally. Also, this total length reduces by 1 m with every 90°
bends or two 45° bends. Maximum 3 pieces of 90° bend can be used.
2.2.13. Installation with Horizontal Flue Sets
Your combi can also be vertically connected to flat and sloping
roofs via available connection accessories depending on the status
of installation place. For flat connections, 5 meters height is acquired
with (Ø 60/100 mm) vertical flue set and, 5 meters with (Ø 60/100 mm)
vertical flue set.
a- Standard Flue Set Bend (45°)
b- Flue Extension Pipe
c- Additional 90° Bend
d- Standard Flue Set Pipe
Figure 16
II. Two 90° bended sample flue installations
d
a
b
c
a + b + c + d < 4 m.
Figure 14
Installation of reduction stamp
Pipe Lengths (m)
Reduction
0 < L < 1
1 < L < 5
Exhaust Gas
Relief
Place the reduction
No reduction stamp
Figure 15
I. Single 90° bended sample flue installation
a
d
b
Lmax = 5m
Figure 17
III. Single 90° and two 45° bended
sample flue installations
d
f
e
b c
a
a + b + c + d + e + f < 4 m.
a- Standard Flue Set Bend (45°)
b- Flue Extension Pipe
c- Additional 45° Bend
d- Standard Flue Set Pipe
e- Additional 45° Bend
f- Standard Flue Set Pipe
Figure 18
Vertical flue set installation
Ø
60
/1
00 mm
= L
ma
x. =
5 m
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
I
I
J
J
K
K
L
L
SHEET
1 OF 1
DRAWN
CHECKED
QA
MFG
APPROVED
ertan biner
15.7.2016
DWG NO
TITLE
SIZE
A0
SCALE
REV
1 / 1
Summary of Contents for LAWA
Page 1: ...CONVENTIONAL COMBI BOILERS INSTALLATION USER MANUAL LAWA LAWAPLUS...
Page 2: ...Lawa LawaPlus Enerwa E24 EnerwaPLUSE24...
Page 25: ...25...
Page 26: ...26...
Page 27: ...27...