BEFORE INSTALLATION
With a digital multimeter measure the resistance of the cable between the two
leads, (
Black
wire and
Red
wire or
Black
wire and
White
wire) see
(FIGURE
2)
. The resistance of each cable should be within 2 percent of the value in
Table
1).
The measurement should agree with the value marked on the cold lead of the
cable. Record this value on the warranty page.( page 22 )
If the resistance does not match the resistance
Of the specific cable you have purchased, please
Contact your
WARM SURFACES
Representative
With a
Megohmmeter
measure the insulation resistance between the
Black
wire
and the
Green
wire. The insulation resistance must not be less than 1000
megohms. Record this value on the warranty page. (page 22 )
If you have measured less than 1000 megohms of resistance between the
Black
and
Green
wires,
Do not connect
the cable
, contact your
WARM
SURFACES™
Representative.
Figure 3
Figure 2
Proper knowledge of test
equipment is required.
Electrical shock may occur.