890564_c•en•01.08.2013
We reserve the right to carry out improvements
44
Wisotronic 2/3/4-channel
Installation instructions
Connection
6.3.7 Locking contact/building
control system
Each channel has a connection available for a separate locking contact. The
contact is used to lock the automatic and manual operation of the connected
products. The contacts are parameterised in the corresponding menus.
Input V1 can be used for the building control system. In the menu you can
define how the individual channels respond to a BCS signal. BCS is active
when the contact is open.
JY (St) Y 2x2x0.8 mm ø
max. 200 m
Wisotronic
power unit
1
2
3 4
5
6
7 8
9
1
2
3 4
5
6
7 8
9
1
2
3 4
5
6
7 8
9
9
S1
BCS
Fig. 24
Connection of the locking contacts/building control system
Terminals blocks X7
Permissible line cross section
0.2 to 2.5 mm
2
single-wire
0.2 to 2.5 mm
2
fine wire
Stripping length
6.5 mm
Maximum line length
200 m
Only use lines of type JY(St)Y 2x2x0.8 mm.
If the window is closed, the contact (S1, closer) is closed and operation is
enabled. If the window is open, the contact is open and cannot be operated.