WAREMA Quatronic dialog

®

 

Operating instructions

7.2   awn/dusk control

The dawn/dusk control comfort function gives you the option of raising the 

sun shading products on your building at dawn and lowering them at dusk, 

and to program this behaviour individually for spring, summer, autumn and 

winter days. The Quatronic dialog can determine, on the basis of changes in 

brightness and intensity, whether the sun is rising or setting, without being 

deceived by a cloud that temporarily obscures the sun. The dawn/dusk con-

trol and the sun control both use the daytime or nighttime brightness values 

via the connected photo sensor. The dawn/dusk control only uses the light 

values between 0 and 99 Lux, while the sun control relies on the values be-

tween 1,000 and 99,999 Lux.

Limit value Dusk

Brightness in Lux (Lx)

Limit value sun

Limit value cloud

Limit value Dawn

 

15000

30

80

99

1000

35000

99000

Dusk

Night

Day

Cloud

Sun

Down command

Down command

Up command

Night

Dawn

Night

Dawn/Dusk

Up command

Sun control

Dawn/dusk control

If the reading at dusk falls below the dusk limit value, a fixed on delay of five 

minutes is triggered.

Brightness display: The upper line shows the brightness in Lux. 

Dusk

 flashes 

in the status line:

Brightness:      10kLx  20Lx  20Lx  50Lx

Status:          Cloud  Dusk  Dusk  Dawn

When the on delay expires, the sun shading products are lowered.  A "dusk 

DOWN phase" is then active for the entire night. A turning procedure is never 

performed. (Reason: roller shutters should not have spaces between the 

slats.)

The display automatically changes to 

Position

 and 

Cause

:

Position:        Lower   

   Upper Upper 

Cause:           ManOp  Sun  Rain  ManOp 

If 

Dusk

 is set for the 

MoFrD

 (= Monday to Friday, off) or 

SaSuD

 (= Saturday 

and Sunday, off) comfort timer, the sun, temperature and humidity controls 

are switched off as well.

If the photo sensor exceeds the set 

Dawn

 limit value, a fixed off delay of five 

minutes is triggered.

Brightness

 display: The upper line shows the brightness in Lux. 

Dawn

 flash-

es in the status line:

Brightness:      10kLx  50Lx  20Lx  50Lx

Status:          Cloud  Dawn  Dusk  Dawn

When the off delay expires, the sun shading products are raised. A "dawn UP 

phase" is then active.

 omfort functions 

 awn/ usk control

Summary of Contents for Quatronic dialog

Page 1: ...WAREMA Quatronic dialog Operating instructions Keep for future use Sun Light WAREMA Valid from 21 March 2011 890362_b en Photo Habermaass GmbH...

Page 2: ...pective installation and ope rating instructions Head office WAREMA Renkhoff SE Hans Wilhelm Renkhoff Strasse 2 97828 Marktheidenfeld Germany P O Box 13 55 97822 Marktheidenfeld Main Ger many Phone 49...

Page 3: ...enus 17 5 1 1 Wind speed and time 18 5 1 2 Brightness dawn dusk 19 5 1 3 Position and Cause 20 5 1 4 Outside temperature and relative humidity 21 5 1 5 Inside temperature 21 5 1 6 Comfort functions on...

Page 4: ...ion 50 7 5 Time switch control 51 7 5 1 Switching on the time switch control 52 7 6 Comfort timer 53 7 6 1 Setting the comfort timer 54 7 6 2 MoFrE MoFrD SaSuE SaSuD 55 7 6 3 Manual operation 56 8 Gen...

Page 5: ...basis Safety functions and comfort functions The Quatronic dialog controls your sun shading product on the basis of the following variables Wind Precipitation Brightness Inside and outside temperature...

Page 6: ...pes depending on the level of poten tial danger DANGE warns of an imminently dangerous situation Possible consequences may include serious or fatal injury personal injury and property or environmental...

Page 7: ...rts WARNIN Commissioning or operation by insufficiently qualified and knowledgeable persons may cause serious damage to the system or even personal injuries Commissioning may therefore only be perform...

Page 8: ...de energized state Make sure that the unit has been sufficiently secured against unauthorized or unintentional reactivation In any case use suitable safety devices for personal protection Never place...

Page 9: ...y your dealer s service department of the malfunction CAUTIO The entire unit becomes non functional if power fails In this case your sun protection visual privacy unit can no longer be protected again...

Page 10: ...age due to the weather conditions All parameters were set correctly during commissioning 3 1 Operational readiness Approx 5 minutes after the supply voltage is switched on the current time day of the...

Page 11: ...unctions of the WAREMA Quatronic dialog can be differ entiated into safety and comfort functions Safety functions Wind monitor Rain monitor Ice monitor Comfort functions Sun control Dawn dusk control...

Page 12: ...read and set on the WAREMA Quatronic dialog For example you can read current measured values of outside brightness outside temperature the current time and much more b disp prog button Display program...

Page 13: ...ation is performed using the arrow buttons on the corre sponding facade The display then changes to Position and Cause The cause is displayed as ManOp See also Chapter 5 1 3 on page 20 4 3 1 Awnings p...

Page 14: ...ion Press the button for approx 2 seconds Position Upper Upper Lower Cause Rain Wind Sun ManOp After the DOWN run time elapses the slats are adjusted to the preselected slat angle see Chapter 8 2 on p...

Page 15: ...ing system is protected against damage due to the weather conditions at all times Comfort functions are Sun control Dawn dusk control Temperature control Humidity control Time switch control Comfort t...

Page 16: ...ion menus The Quatronic dialog has two selection menus Here you can select the functions of the Quatronic dialog that you wish to set Select a function group using the buttons Press the button under t...

Page 17: ...ously Press the disp prog button to change to the next menu Wind speed and time m s h min Brightness kLx dawn dusk Lx Position and cause Outside temperature and relative humidity C Frel Inside tempera...

Page 18: ...way 10 8 13 8 6 Strong wind whistling noise on wires 13 9 17 1 7 Stiff wind perceivable hindrance when walking 17 2 20 7 8 Stormy wind twigs break off trees walking is quite difficult 20 8 24 4 9 Stor...

Page 19: ...ue Sun Reading exceeded DOWN sun limit value Dusk Dawn dusk Reading dropped below DOWN limit value Dawn Dawn dusk Reading exceeded UP limit value Night Dawn dusk Reading dropped below DOWN limit value...

Page 20: ...ly displays the move command that was last issued Lower line Indicates what triggered the last move command Possible causes are Display Meaning Wind Wind monitoring safety function Ice Ice monitoring...

Page 21: ...display the humidity at each facade a sensor must be connected for each facade Lower line Associated conditions where the following displays are pos sible Display Meaning Cold Reading dropped below lo...

Page 22: ...election menu is displayed Select the Wind RunT Timer Sun settings Rain Temp Product Press the button under to open the second page of the selection menu Select the Displ Ice ComfT Time settings Passw...

Page 23: ...tect the controlled sun shad ing products against damage due to the weather conditions All parameters were set correctly during commissioning Keep the disp prog button pressed for approx 5 seconds Win...

Page 24: ...Temperature control Humidity Humidity control Clock Time switch control Auto Comfort timer General parameters see Chapter 8 on page 57 Product Set the type of connected product Run time Run time and...

Page 25: ...e settings for each facade F1 F4 using the buttons Temp outside OFF OFF OFF OFF Limit CH1 CH2 CH3 CH4 Leave the menu after completing the entries using the disp prog button This saves the changes you...

Page 26: ...venetian blinds against storm damage In a windstorm the sun shading products are automatically raised and can be lowered neither by hand not by the comfort functions sun control time switch Whether or...

Page 27: ...m s 8m s Time 10 26 47 Wednesday 20 11 2008 The selection menu is displayed Select the Wind RunT Timer Sun settings Rain Temp Product Press the button above the word Wind The Wind menu is displayed Wi...

Page 28: ...peed drops below the set limit value before the on delay expires the on delay stops running The next time the limit value is exceeded the on delay begins running again from zero If the wind speed rema...

Page 29: ...onnected Sensor Wind 1 Sensor Wind 2 Facade 1 Facade 2 Facade 4 Facade 3 You connect an additional wind sensor see the installation instructions as sensor 2 that you would like to allocate to facade 3...

Page 30: ...sensor in 99 hours it is assumed that the sensor is defective All sun shading products for which the wind test is active are raised The following message appears in the display of the Quatronic dialo...

Page 31: ...tian blinds and roller shutters When precipitation rain snow drizzle falls on the precipitation sensor the sun shading products are raised The preselected comfort functions and manual operation are lo...

Page 32: ...y 20 11 2008 The selection menu is displayed Select the Wind RunT Timer Sun settings Rain Temp Product Press the button below the word Rain The Rain monitoring ON OFF menu is displayed Rain monitoring...

Page 33: ...disp prog button pressed for approx 5 seconds Wind speed 8m s 8m s 8m s 8m s Time 10 26 47 Wednesday 20 11 2008 The selection menu is displayed Select the Wind RunT Timer Sun settings Rain Temp Produc...

Page 34: ...the facades with ice monitoring all comfort functions are blocked during an ice alarm However you can use the buttons to open the Ice menu on these facades ICE ALERT Reset the ice alert until next ic...

Page 35: ...his feature is provided for use if you discover that the sun shading products are already frozen after you previously switched off the ice monitor To execute an emergency stop press one of the arrow b...

Page 36: ...abled Now disconnect the Quatronic dialog and the motor control units from the 230 V voltage using the in series circuit breaker to prevent the sun shading products from being operated locally After y...

Page 37: ...of the sunlight is measured by the Quatronic dialog using four photo sensors that are integrated in the wind sensor If the photo reading exceeds the set DOWN limit the on delay begins run ning The fol...

Page 38: ...pper Upper Cause ManOp Sun Rain ManOp If the sun shading products are raised or lowered by hand there is no reac tion from the sun control until the next change in the light conditions NOTE The sun co...

Page 39: ...8m s 8m s 8m s Time 10 26 47 Wednesday 20 11 2008 The selection menu is displayed Select the Wind RunT Timer Sun settings Rain Temp Product Press the button above the word Sun The Sun menu is displaye...

Page 40: ...ps running If the photo reading drops below the UP limit value the off delay begins run ning If the reading continues to lie below the UP limit value the sun shading prod uct is raised after the off d...

Page 41: ...u can now assign one or all photo sensors to each of your facades Photo sensor 1 4 2 3 4 allocation CH1 CH2 CH3 CH4 When shading the roof of a conservatory it is recommended to assign sen sors 1 4 to...

Page 42: ...ommand Night Dawn Night Dawn Dusk Up command Sun control Dawn dusk control If the reading at dusk falls below the dusk limit value a fixed on delay of five minutes is triggered Brightness display The...

Page 43: ...ts are lowered during the dusk DOWN phase e g at night 7 2 1 Setting the dawn dusk control To open the menu for the dawn dusk control keep the disp prog button pressed for approx 5 seconds Keep the di...

Page 44: ...fa cade Leave the menu after completing the entries using the disp prog button This saves the changes you made 7 2 2 Dusk dawn The effects of the settings are addressed below in more detail The Dusk...

Page 45: ...trol the effects of the light and heat produced by the sun s radiation The two operating modes of the temperature control are The temperature control triggers an UP DOWN move command The temperature c...

Page 46: ...n InOM control settings Out In OutOM Alloc Select the desired parameter by pressing the or button Example Outside temperature limit value for the up command In this menu you can change the settings fo...

Page 47: ...perature control triggers an UP move command The display then changes to Position and Cause Position Upper Upper Cause Temp Rain Rain Temp The following display appears after the move command is compl...

Page 48: ...ed on If the temperature reading drops below the UP limit value an UP move com mand is triggered or the sun control is switched off and an UP move com mand is triggered NOTE The temperature control ha...

Page 49: ...Cause Position Upper Upper Cause rel H Rain Rain rel H The following display appears after the move command is completed Position Lower Upper Upper Lower Cause rel H Rain Rain rel H If the humidity dr...

Page 50: ...ed by setting the value to 0 The word OFF appears instead of 0 This switches off the humidity control at the respective facade Leave the menu after completing the entries using the disp prog button Th...

Page 51: ...ommands NOTE Time switch control is deactivated by default When the time set under MoFr or SaSu is reached the sun shading prod ucts move up The timer UP phase is then active The following display app...

Page 52: ...s displayed Timer switch stands for time switch control Timer switch MoFr SaSu settings MoFr SaSu Select the desired parameter by pressing the or button Example UP command on a weekday MoFr In this me...

Page 53: ...provides a comfort timer feature This feature lets you control all comfort functions on the basis of the time of day You can also differentiate between weekdays and weekends If you need to switch off...

Page 54: ...for approx 5 seconds Wind speed 8m s 8m s 8m s 8m s Time 10 26 47 Wednesday 20 11 2008 The selection menu is displayed Select the Wind RunT Timer Sun settings Rain Temp Product Press the button under...

Page 55: ...ues you can enter the times during which the comfort timer should enable the comfort functions MoFrD SaSuD Using the Comfort functions OFF on a weekday MoFrD and Comfort func tions OFF on a weekend Sa...

Page 56: ...rt functions globally at the Quatronic dialogue without having to change your other settings You have two possibilities 1 Switch off the comfort functions in the Comfort timer settings Manual menu ite...

Page 57: ...ng rou tine it set the products on all facades to the articulated arm awning for safety reasons To adapt the Quatronic dialog to your needs you can now set up the products roller shutters external ven...

Page 58: ...ts Keep the disp prog button pressed for approx 5 seconds Wind speed 8m s 8m s 8m s 8m s Time 10 26 47 Wednesday 20 11 2008 The selection menu is displayed Select the Wind RunT Timer Sun settings Rain...

Page 59: ...sun shading product is set to an average value at the fac tory It can be adjusted to the run time of the product actually in use see the Factory settings chapter in the installation instructions 8 2 1...

Page 60: ...ou made 8 2 2 Run time UP DOWN The move command is active for the set run time which means that if the run time is too short the sun shading product does not move all the way to the limit position By...

Page 61: ...turning takes place When using the External venetian blind or Pleated blind product set ting the turn setting can be used to set a slat angle of your choice The turn time can also be used to open roll...

Page 62: ...o be displayed for approx 5 minutes even after the supply voltage is switched off Keep the disp prog button pressed for approx 5 seconds Wind speed 8m s 8m s 8m s 8m s Time 10 26 47 Wednesday 20 11 20...

Page 63: ...sible to everyone Switching on and off of the comfort functions by hand in the 6th display see Chapter Displays is generally not protected by the password 8 4 1 Defining the password Keep the disp pro...

Page 64: ...ay mode 8 4 2 Opening the programming level with the password If the Quatronic dialog is protected by a password you can only enter the programming level if you know the password Perform the following...

Page 65: ...entered the old password you are asked for the new password Please enter new password 0 0 0 0 Enter the new password using the buttons Leave the menu after completing the entries using the disp prog b...

Page 66: ...or each channel Press the info button again to leaf through the help text This delay is required so that brief exceeding of the wind limit does not If there are no additional pages the following messa...

Page 67: ...ner that contravenes its intended use and purpose may result in the manufacture refusing to honour warranty claims for product dam age In this case liability for consequential harm to persons or damag...

Page 68: ...d cannot be low ered manually Wind monitor If the wind alarm is unfounded in crease the limit value Ice monitor The ice monitor can be disabled at your own risk Chapter 6 3 on page 33 Rain monitor In...

Page 69: ...Reduce the off delay Chapter 7 1 on page 37 Sun shading product moves up too early when cloudy UP sun limit value Lim too low Sun control Lim menu Increase the UP sun limit value Chapter 7 1 on page...

Page 70: ...ux 30 30 15 OFF 30 Limit value sun down kLux 50 50 35 OFF 50 On delay Min 5 5 2 OFF 5 Off delay Min 10 10 20 OFF 10 Dawn dusk Dusk down Lux OFF OFF OFF 80 OFF Dawn up Lux OFF OFF OFF 30 OFF Rain monit...

Page 71: ...Min Sun Limit value clouds up kLux Limit value sun down kLux On delay Min Off delay Min Dawn dusk Dusk down Lux Dawn up Lux Rain monitor On off Temperature Outside limit value up C Outside limit value...

Page 72: ...WAREMA Renkhoff SE Hans Wilhelm Renkhoff Strasse 2 97828 Marktheidenfeld Germany http www warema de info warema de...

Reviews: