Installation
The W440 AIS Sart Sniffer can be installed on DIN guide (standard model)
or on wall using an adapter kit (on request).
Please note that the W440 is not a waterproof device, and shall be
installed on a protected area.
After W440 mechanical installation, you can connect the AIS Sart Sniffer
using copper wire with almost 0.75 mm
2
size.
We suggest to use the schematic diagram on page 4.
In detail, as for the wire connector marked as (1) (upper part), please see
the following connections :
Pin
Connection type and function
1
Positive DC power supply (max +30 Volts)
2
Ground or negative
3
Rotary knob switch lamp.
4
C type rotary knob switch contact (spring return)
5
B type rotary knob switch contact (common)
6
A type rotary knob switch contact (ON mode)
7
N.O. relay contact
8
Common relay contact
9
N.C. relay contact
8
EN