Fuel Lines & Filters

 

 
Wallas diesel products come with 
polyethylene fuel line kits shipped in the 
carton, which include a fuel filter & 
miscellaneous adapters.   
 
If you purchase a Wallas day tank, these 
fuel line kits are not used, being replaced 
by a complete #367215 tank adapter kit.  
The #367215 kit has it’s own tank end filter.  
Only one filter should be used. 
 
The fuel lines are attached to the furnace 
using a three part compression fitting, 
shown in the images to the right.  Correct 
first assembly of the fuel line fitting and 
mounting to the Wallas appliance is very 
important. 
 

1.

 

Make sure the fuel line end is cut 
cleanly and squarely. 

2.

 

Slide the nut on the fuel line, with 
the threads toward the line end. 

3.

 

Push the acorn over the end of 
the fuel line. 

4.

 

Slide the ferrule into the end of 
the fuel line until the flange sits 
snugly against the plastic tube. 

5.

 

Check the fuel fitting on the 
Wallas product and the 
acorn/ferrule end, making sure 
they are clean and free of debris. 

6.

 

Place the end of the acorn 
against the Wallas product’s fuel 
fitting and slide the nut against 
the threads. 

7.

 

Spin the nut onto the threads and 
tighten very firmly.  This process 
compresses the fitting. 

8.

 

Loosen the nut and re-tighten for 
a fully sealed fit. 

 

Please note:  ABYC and NMMA rules 
may require the use of fire rated fuel 
lines in new vessel applications.  Please 
contact Scan Marine for these products 
and their correct application. 

Summary of Contents for Nautic 40D

Page 1: ...WALLAS 40D Operator s Manual and Installation Guide 1 2010 Two Mac Inc...

Page 2: ...el options include a Basic Control Panel with indicator lamps or a Digital Info Control Panel The furnace is made entirely of marine grade materials Table 1 Technical details of furnace 40D TECHNICAL...

Page 3: ...tantly at an angle The installation must maintain a minimum of 8 inches under the furnace to facilitate maintenance otherwise removal of the unit will be necessary for maintenance To avoid galvanic co...

Page 4: ...wo M8 x 120 locking bolts Figure 6 Attaching the control panel Note either the 3004 or 3005 can be mounted with or without the bezel shown here 3005 panel must have the bezel fitted for thermostat to...

Page 5: ...WALLAS 40D Operator s Manual and Installation Guide 5...

Page 6: ...WALLAS 40D Operator s Manual and Installation Guide 6...

Page 7: ...n order to secure sufficient air flow the heating air must be divided into at least three outlet vents The ducting attaches to two 3 inch 75mm outlet adaptors at the end of the furnace The longest per...

Page 8: ...safety reasons the furnace must not be installed In a place where gasoline fumes might be present The suction air is taken in via two branches of ducting One inlet duct should take in some fresh air...

Page 9: ...e the power switch to the OFF position The furnace cannot be restarted until the cooling fans have stopped and all indicator lamps have gone out Once the indicator lamps have gone out restart the furn...

Page 10: ......

Page 11: ...at When installing please note the thermostat manufacturer s instructions The thermostat will not switch the furnace on or off but will adjust the furnace between minimum power and the user determined...

Page 12: ...WALLAS 40D Operator s Manual and Installation Guide 12 Figure 15 Figure 14...

Page 13: ...mportant 1 Make sure the fuel line end is cut cleanly and squarely 2 Slide the nut on the fuel line with the threads toward the line end 3 Push the acorn over the end of the fuel line 4 Slide the ferr...

Page 14: ...ngine pickup Install a filter in the fuel line Note the need for replacing the fitter periodically Cut the fuel line to a suitable length during installation Ensure that the fuel line joint surfaces a...

Page 15: ...thout the consent of the manufacturer The instructions for installation operation or maintenance have not been followed Storage or transport has been inappropriate A problem has resulted from an accid...

Page 16: ...WALLAS 40D Operator s Manual and Installation Guide 16 June 2 2010...

Reviews: