765-2704/200-000
Diagnostics
30
Product manual | Version: 1.0.0
2AO FLD IOL CONV 0-10V
11
Diagnostics
11.1 Diagnostics via Indicators
Table 37: Diagnostics via Indicators
LED
LED State
Explanation
I
On
The analog value is in the normal range:
0 ... 100 % (0 ... 10 V)
Flashing (2 Hz) The analog value is in the range:
100 ... 110 % (10 ... 11 V)
Flashing (5 Hz) There is a short circuit or overload at the output.
POWER
On
The supply voltage is OK.
The product is in operating mode.
Flashing (5 Hz) The supply voltage is too low.
Off
There is no supply voltage.
II
On
The analog value is in the normal range:
0 ... 100 % (0 ... 10 V)
Flashing (2 Hz) The analog value is in the range:
100 ... 110 % (10 ... 11 V)
Flashing (5 Hz) There is a short circuit or overload at the output.
11.2 Diagnostics via IO-Link
11.2.1 Diagnostics
Table 38: Variables – Diagnostics – General
Index
36
Access rights
Read-only
Table 39: Variables – Diagnostics
Name
Description
Subindex Data
Type
Length
Factory
Setting
Value Range
Device status
Indicates the
current product
and diagnostic
state
0
UIntegerT 8 bits
0
0 (Product is OK)
1 (Maintenance required)
2 (Outside specification)
3 (Function test)
4 (Failure)
5 ... 255 (Reserved)
11.2.2 Detailed Diagnostics
Table 40: Variables – Detailed Diagnostics – General
Index
37
Access rights
Read-only