2AO FLD IOL CONV 0-10V
6
Planning
6.1 Structure Guidelines
6.1.1 Overcurrent Protection
Protecting Circuits against Overcurrent
Protect the circuits by using a fuse.
Table 35: Protecting Circuits against Overcurrent
Potential
M12 A plug
Fuse
1L+ / power supply
Pin 1
≤2 A
C/Q IO-Link
(if not fused via IO-Link master)
Pin 4
≤2 A
Required trip characteristics of the fuses:
T
fuse
≤120 s at max. 6.25 A (fire protection)
Alternatively, the product can be powered by a limited-energy circuit per IEC 61010-1 or
Class 2 per UL 1310.
CAUTION
The input current is unrestricted.
> no fire protection
•
Protect circuits against overcurrent.
6.1.2 EMC Installation
•
Keep data and signal lines separate from interference sources.
Route data and signal lines separately from all power supply cables and other sources
of high electromagnetic emissions (e.g., frequency converters or drives).
•
Observe maximum cable lengths
The maximum lengths of the connecting cables are as follows:
– With IO-Link communication on the product master side: 20 m